Connecting Logo! And The Digital Modules To 230 V - Siemens LOGO! 8 Manual

Tde central control for individual switching of general consumers
Hide thumbs Also See for LOGO! 8:
Table of Contents
3 Commissioning
3.3

Connecting LOGO! and the digital modules to 230 V

Multi-phase operation
Not observing the following instructions can lead to injury!
The expansion modules DM8 230R and DM16 230R must be operated with the
same type of power supply (DC or AC) as the connected 230V version of the
CAUTION
LOGO! basic module!
The same supply output "+/-" (direct voltage) or "N/L" (alternating voltage) must
be connected to the same phase on both the DM8/16 230R expansion module
and the connected LOGO! basic unit!
The LOGO! 230RCE features 8 digital inputs in two groups.
Within a group, the same phase must be used at all inputs. Different phases are
only possible between the groups!
This means that you use the four inputs [I1-I4] on phase L1 and the four inputs [I5-
I8] on phase L2 according to
The digital module DM16 230R is also divided into two groups.
Digital modules can only be connected to devices with the same voltage class,
here 230V for the LOGO! 230RCE.
Figure 3-2: Multi-phase operation with one basic device and four digital modules
L1
L2
L3
N
This application example provides the maximum configuration for a LOGO! 8
Note
with 20 outputs. However, only 20 inputs are used for switching. [I21] to [I24] are
not used!
LOGO! 8 TDE Central control for individual switching of general consumers
Entry ID: 109755864,
V1.0,
Figure
L1 N I1 I2 I3 I4
I5 I6 I7 I8
L1 N I9 I10 I11 I12
X10
LOGO! 230RCE
DM16 230R
LOGO! 8 in
Building
Technologies
Q5
X11
Q1
Q2
Q3
Q4
Q7
Example representation of individual consumers
04/2018
3-2, for example.
I13 I14 I15 I16
L1 N I17 I18 I19 I20
DM8 230R
Q6
Q9
Q13
Q14
Q10
Q8
Q11
Q12
Q15
Q16
L1 N I21 I22 I23 I24
DM8 230R
Q17
Q18
Q19
Q20
L1
L2
L3
N
9