Burner controls for the supervision of 1- or 2-stage gas or gas / oil burners of
small to medium capacity, operation, with or without fan in intermittent (26 pages)
LME Series Technical Instructions Document No. LME-1000 Table of Contents Section 1: Overview Introduction ........................... 1 LME7 System Builder ......................2 Mounting ..........................10 Important Safety Notes ......................12 Approvals ..........................13 Section 2: LME71 Wiring, Parameters, and Phase Diagrams LME71 Wiring Diagrams ......................
Page 4
Technical Instructions LME Series Document No. LME-1000 Section 6: PWM Blowers Introduction ........................... 1 PWM Blower Fundamentals ....................1 Centrifugal Blower Fundamentals ..................2 Blower Speed Monitoring ...................... 3 Commissioning the LME7 when Using a PWM Blower............5 Adjusting P0, P1, and P2 via the LME7 Built-in Display ............7 Adjusting P0, P1, and P2 via the AZL23 Display Unit ...............
Page 5
LME Series Technical Instructions Document No. LME-1000 Section 9: ACS410 ACS410 Software Introduction ....................1 Software Installation ......................2 Connecting to a PC ......................... 3 Saving a Parameter Set to a PC ....................4 Uploading a Parameter Set to an LME7 .................. 5 Creating an LME7 Startup Report ...................
Page 6
Technical Instructions LME Series Document No. LME-1000 Intentionally Left Blank Table of Contents Page 4 SCC Inc.
LME Series Technical Instructions Document No. LME-1000 Introduction The LME7 burner control is ideally suited for use in industrial thermal process applications. The LME7 is extremely flexible, and encompasses the following features: • Accepts standard UV, self-check UV, or self-check IR scanners and/or flame rods •...
Technical Instructions LME Series Document No. LME-1000 LME7 System Builder The LME7 burner control system is comprised of many components. Use the following pages to choose the components needed for your specific application. Control Panel Components Base Unit – Qty (1) Required Choose one of the following LME7 base unit options.
Page 11
LME Series Technical Instructions Document No. LME-1000 Plug Set – Qty (1) Required The terminal plug set for the LME7 is sold separately. Each LME7 needs one plug set. Plug set containing all terminals for an LME7 system AGG3.710 LME7 Package - Optional For convenience, the LME7 base unit, PME7 program module, and AGG3.710 plug set can be ordered as a package that is shipped pre-assembled.
Page 12
Technical Instructions LME Series Document No. LME-1000 Remote Display – Optional Each LME7 can be equipped with a remote display that provides additional status information not shown by the integral LED display on the LME7. Either the remote display or the ACS410 software are required to change parameter settings on the LME7.
Page 13
LME Series Technical Instructions Document No. LME-1000 Actuators and Accessories Actuator – Qty (1) Optional with LME73 and LME75 Burner Controls SQM4… and SQM5… series actuators are available for use with the LME73 and LME75 burner controls. For more information on SQM4… actuators, refer to Document No. N7817. For more information on SQM5…...
Page 14
Technical Instructions LME Series Document No. LME-1000 Flame Scanners Flame Scanners – Qty (1) Required Unless Using a Flame Rod Four flame scanners are available for use with the LME7. For technical information about these flame scanners, refer to Document No. N7711 for the QRA4.U, Document No. N7719 for the QRI…...
Page 15
LME Series Technical Instructions Document No. LME-1000 QRA75.A17 Accessories - Optional Mounting accessories are available for the QRA75.A17 flame scanner. For more information, refer to Document No. N7712. Right angle adapter for mounting a QRA75 flame scanner. Comes with a 1” NPSM female thread AGG16.U connection Thermal barrier for use with the QRA75 flame...
Page 16
Technical Instructions LME Series Document No. LME-1000 Additional Flame Scanner Accessories – Optional Additional accessories are available for flame scanners to prevent heat from getting to the scanner. For more information, refer to Document No. N7711 and Document No. N7712. Thermal barrier for use with the QRA4.U flame scanner, and QRI2B2.B180B flame scanner when THERMAL-...
Page 17
LME Series Technical Instructions Document No. LME-1000 Enclosures Enclosures - Optional A small NEMA 1 enclosure is available for use with any LME7… base unit. Three ½” conduit knockouts are available on both the top and the bottom of the enclosure. NEMA 1 enclosure for any LME7…...
Technical Instructions LME Series Document No. LME-1000 Mounting LME7 Controller The LME7 must be mounted inside an enclosure that will protect it from dirt and moisture. The unit should be mounted with three #8 screws (not provided). The panel, which the unit sits on, should be drilled and tapped to accommodate these screws.
Page 19
LME Series Technical Instructions Document No. LME-1000 AZL23 Display The AZL23 is designed to be mounted in a rectangular cutout through the face / door of an electrical enclosure. It has one screw on the top and another on the bottom that engage small plastic tabs which will swing out when the screw is tightened clockwise;...
Technical Instructions LME Series Document No. LME-1000 Important Safety Notes • The LME7 is a safety device. Under no circumstances should the unit be modified or opened. SCC Inc. will not assume responsibility for damage resulting from unauthorized modification of the unit. •...
LME Series Technical Instructions LME-1000 LME71 Wiring Diagrams PME71.111A1 – Pilot or direct spark; with purge; no actuator control; no valve proving SCC Inc. Page 1 Section 2...
Page 26
Technical Instructions LME Series Document No. LME-1000 PME71.112A1 – Pilot or direct spark; no purge; no actuator control; no valve proving Section 2 Page 2 SCC Inc.
Page 27
LME Series Technical Instructions LME-1000 PME71.901A1 – PWM blower control; direct spark only; valve proving; no actuator control SCC Inc. Page 3 Section 2...
Technical Instructions LME Series LME71 Parameter List LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME71. PME71. PME71. Shaded Parameters = Frequently Used Parameter Name Number 111A1...
Page 29
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME71. PME71. PME71. Shaded Parameters = Frequently Used Parameter Name Number 111A1...
Page 30
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME71. PME71. PME71. Shaded Parameters = Frequently Used Parameter Name Number 111A1...
Page 31
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME71. PME71. PME71. Shaded Parameters = Frequently Used Parameter Name Number 111A1...
Page 32
Defines the device being controlled by the LME7 that is used to influence the amount of air to the burner. This value is set by Siemens and cannot be modified. On PME71.901A1, this value should always be set to Read only •...
Page 33
Max Ramp Down For Siemens use only. Sets the maximum allowable value for the ramp down time (parameter 523). For Siemens use only. Sets the amount of time the blower speed can lie outside of tolerance band 1 • Tolerance Band 1 Time before a lockout occurs.
Page 34
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME71. PME71. PME71. Shaded Parameters = Frequently Used Parameter Name Number 111A1...
Technical Instructions LME-1000 LME71 Phase Diagrams The Siemens LME7 burner controls can perform a number of different burner sequences based upon which PME7 program module is used, how certain parameters are set, and how the LME7 is wired. Each program module has an associated phase diagram. The phase diagrams illustrate when input and output terminals are expected to be energized or de-energized.
Page 36
LME Series Technical Instructions LME-1000 PME71.111A1 Phase Diagram Phase Param. OPER- STARTUP SHUTDOWN ATION SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch X5-01.2 Gas Pressure Switch(es) X10-05.2 Flame Signal X10-06.1/2 POC (P237 = 1) X2-02.4...
Page 37
LME Series Technical Instructions LME-1000 PME71.112A1 Phase Diagram Phase Param. OPER- STARTUP SHUTDOWN ATION SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X5-01.2 Gas Pressure Switch(es) X10-05.2 Flame Signal X10-06.1/2 POC (P237 = 1) X2-02.4 POC (P237 = 2) X2-02.3...
Page 38
Technical Instructions LME Series LME-1000 PME71.901A1 Phase Diagram Phase Param. OPER- STARTUP SHUTDOWN VALVE PROVING ATION SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch X5-01.2 Gas Pressure Switch(es) X9-04.2 Valve Proving Pressure Switch X10-05.2 Flame Signal...
LME Series Technical Instructions LME-1000 LME73 Wiring Diagrams PME73.811A1 – Modulating actuator control with valve proving; ignition position = low fire SCC Inc. Page 1 Section 3...
Page 42
Technical Instructions LME Series Document No. LME-1000 PME73.812A1 – Modulating actuator control with independent ignition position; no valve proving Section 3 Page 2 SCC Inc.
Page 43
LME Series Technical Instructions LME-1000 PME73.840A1 – Floating/bumping (position proportional) actuator control with valve proving; actuator can be disabled; ignition position = low fire SCC Inc. Page 3 Section 3...
Technical Instructions LME Series LME73 Parameter List LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME73. PME73. PME73. Shaded Parameters = Frequently Used Parameter Name Number 811A1...
Page 45
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME73. PME73. PME73. Shaded Parameters = Frequently Used Parameter Name Number 811A1...
Page 46
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME73. PME73. PME73. Shaded Parameters = Frequently Used Parameter Name Number 811A1...
Page 47
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME73. PME73. PME73. Shaded Parameters = Frequently Used Parameter Name Number 811A1...
Page 48
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME73. PME73. PME73. Shaded Parameters = Frequently Used Parameter Name Number 811A1...
Technical Instructions LME-1000 LME73 Phase Diagrams The Siemens LME7 burner controls can perform a number of different burner sequences based upon which PME7 program module is used, how certain parameters are set, and how the LME7 is wired. Each program module has an associated phase diagram. The phase diagrams illustrate when input and output terminals are expected to be energized or de-energized.
Page 50
Technical Instructions LME Series Document No. LME-1000 PME73.811A1 Phase Diagram Phase Param. STARTUP OPERATION SHUTDOWN VALVE PROVING SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch X5-01.2 Gas Pressure Switch(es) X9-04.2 Valve Proving Pressure Switch X10-05.2...
Page 51
LME Series Technical Instructions Document No. LME-1000 PME73.812A1 Phase Diagram Phase Param. STARTUP OPERATION SHUTDOWN SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch X5-01.2 Gas Pressure Switch(es) X10-05.2 Flame Signal X10-06.1/2 POC (P237 = 1) X2-02.4...
Page 52
Technical Instructions LME Series Document No. LME-1000 PME73.840A1 Phase Diagram Phase Param. OPER- STARTUP SHUTDOWN VALVE PROVING ATION SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch X5-01.2 Gas Pressure Switch(es) X9-04.2 Valve Proving Pressure Switch X10-05.2...
LME Series Technical Instructions LME-1000 LME75 Wiring Diagrams PME75.811A1 – Modulating actuator control with valve proving; self-check scanner or flame rod; ignition position = low fire SCC Inc. Page 1 Section 4...
Page 56
Technical Instructions LME Series Document No. LME-1000 PME75.812A1 - Modulating actuator control with independent ignition position; no valve proving; self-check scanner or flame rod Section 4 Page 2 SCC Inc.
Technical Instructions LME Series LME75 Parameter List LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME75. PME75. Shaded Parameters = Frequently Used Parameter Name 811A1 812A1...
Page 58
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME75. PME75. Shaded Parameters = Frequently Used Parameter Name 811A1 812A1 Number...
Page 59
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME75. PME75. Shaded Parameters = Frequently Used Parameter Name 811A1 812A1 Number...
Page 60
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME75. PME75. Shaded Parameters = Frequently Used Parameter Name 811A1 812A1 Number...
Page 61
Technical Instructions LME Series LME-1000 LEGEND - Password Level: S = Service; O = OEM; S/O = View - Service, Write - OEM; Info = Info Menu; Ser = Service Menu Parameter PME75. PME75. Shaded Parameters = Frequently Used Parameter Name 811A1 812A1 Number...
LME Series LME-1000 LME75 Phase Diagrams The Siemens LME7 burner controls can perform a number of different burner sequences based upon which PME7 program module is used, how certain parameters are set, and how the LME7 is wired. Each program module has an associated phase diagram. The phase diagrams illustrate when input and output terminals are expected to be energized or de-energized.
Page 63
Technical Instructions LME Series Document No. LME-1000 PME75.811A1 Phase Diagram Phase Param. STARTUP OPERATION SHUTDOWN VALVE PROVING SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On Air Pressure Switch Note 3 X3-02.1 Gas Pressure Switch(es) Note 4 X5-01.2 X9-04.2...
Page 64
LME Series Technical Instructions Document No. LME-1000 PME75.812A1 Phase Diagram Phase Param. STARTUP OPERATION SHUTDOWN SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch Note 3 X5-01.2 Gas Pressure Switch(es) Note 4 X10-05.1 Flame Signal...
LME Series Technical Instructions Document No. LME-1000 Commissioning a New LME7 Burner Control 1. Ensure all devices are properly connected to the LME7. See Section 2 (LME71…), Section 3 (LME73…), or Section 4 (LME75…) of this manual for more information on wiring devices to the LME7 burner control.
Technical Instructions LME Series Document No. LME-1000 Parameter Backups / Restores Both the LME7 burner control and PME7 program module contain one parameter set. The parameter set in the LME7 burner control is always the one that is used for burner operation. The parameter set in the PME7 program module is simply a backup parameter set.
LME Series Technical Instructions Document No. LME-1000 Parameter Restore (PME7 -> LME7) Using the AZL23 Display Unit Use to overwrite the parameters in the LME7 with those previously saved in the PME7. 1. Press and hold the F and A buttons on the AZL23 until “CodE” is displayed, then release. 2.
Technical Instructions LME Series Document No. LME-1000 Displaying the Actuator Position / PWM Blower Speed from the LME7 Burner Control The current position of the actuator (LME73…/LME75…) or speed of the PWM blower (LME71… with PME71.901A1) can be viewed from the LME7 burner control using the following procedure. 1.
LME Series Technical Instructions Document No. LME-1000 Introduction The LME71 flame safeguard, when used with the PME71.901A1 program module, features an integrated, closed-loop PWM (pulse width modulation) blower control. This integrated control is used to modulate the speed of a PWM blower with firing rate. The LME71 transmits a PWM control signal to the blower, and then reads back the speed of the blower.
Technical Instructions LME Series Document No. LME-1000 Centrifugal Blower Fundamentals Since a centrifugal blower is the piece of machinery being controlled by the LME7, a brief mention of its basic characteristics is warranted. Specifically, there are three fundamental "fan laws" that a person working with such equipment should be aware of.
LME Series Technical Instructions Document No. LME-1000 Blower Speed Monitoring To help ensure that the burner is either operated at a safe fuel-to-air ratio or is shut down, the blower speed is constantly monitored while a flame is present. The speed is monitored in a way that nuisance shutdowns are eliminated, but fast shutdowns will occur if the speed deviation is large.
Page 76
Technical Instructions LME Series Document No. LME-1000 Tolerance Band 1 Tolerance Band 2 Name of Tolerance Band High Limit of Tolerance Band +1.0% to 5.0% +1.0% to 10.0% Low Limit of Speed Band -1.0% to 5.0% -1.0% to 10.0% Parameter to Adjust Width of Band 650.00 650.01 Maximum Blower Speed (P519)
LME Series Technical Instructions Document No. LME-1000 Commissioning the LME7 when Using a PWM Blower After verifying that all PWM blower-related components are installed and wired correctly, the LME7 burner control can be programmed for the PWM blower application. Prerequisites Ensure that the PWM blower is a closed loop type, meaning that it is utilizing an onboard speed •...
Page 78
Technical Instructions LME Series Document No. LME-1000 8. Set the ignition (P0), low fire (P1), and high fire (P2) blower speeds with the burner off. These values are found in the 400 set of parameters. To set these parameters, use the following procedure: a.
LME Series Technical Instructions Document No. LME-1000 Adjusting P0, P1, and P2 via the LME7 Built-in Display 1. While in standby (OFF), press and hold the A button and either the + or - button for more than five seconds until “OFF” starts blinking. 2.
Technical Instructions LME Series Document No. LME-1000 Adjusting P0, P1, and P2 via the AZL23 Display Unit 1. Log in at the Service or OEM access level. The display will say “400: Set”. Press the info button. 2. The display will say “run”. Give the LME7 a call for heat. The LME7 will proceed to start the burner. After prepurge is complete, the LME7 will slow the blower down to the preset ignition speed (P0).
LME Series Technical Instructions Document No. LME-1000 Additional Tips for Burners with PWM Blowers Most of the time, speed faults that are seen on the LME7 are caused by the PWM blower not being • able to decelerate quickly enough when the blower is being ramped down. If fast ramp times are not critical for the application, ramp times (parameters 522 and 523) can be increased and this should correct the issue.
Page 82
Technical Instructions LME Series Document No. LME-1000 Intentionally Left Blank Section 6 Page 10 SCC Inc.
LME Series Technical Instructions Document No. LME-1000 Troubleshooting Introduction The LME7 has an extensive list of fault codes to help clarify the nature of any fault. Section 7-2 describes every fault code in detail and gives guidance on how to correct it. When a fault occurs, the LME7 will alternate between displaying “Loc”...
Page 86
Technical Instructions LME Series Document No. LME-1000 Navigating the Fault History To navigate the fault history, use the following key strokes on the AZL23. • When the parameter number is flashing, press the “+” or “-” button to cycle through the list of faults (parameters 701-711).
Complete Fault Code List Fault Description of the Fault Corrective Action Code A flame failure occurred during lightoff. 1. Check the wiring of the ignition transformer, pilot valve, and main valve(s). 2. Ensure manual shutoff valves on the pilot gas line and main gas line are open. No flame at start-up 3.
Page 88
Fault Description of the Fault Corrective Action Code A flame failure occurred during normal operation. 1. Check the fuel / air ratio. Loss of flame 2. Check the flame detector signal in the presence of a known flame source. Replace the flame detector if it does not produce the anticipated signal.
Page 89
Fault Description of the Fault Corrective Action Code Check all of the switches wired into the safety loop on terminal X3-04.1. One of the switches opened, Safety loop open causing the fault. Fix the condition that caused the switch to open and reset the fault. The 4-20 mA input connected to terminal X65 is out of range.
Page 90
Fault Description of the Fault Corrective Action Code One or more PWM blower settings are not compatible. Make sure the following three conditions on the minimum and maximum speed settings are met. PWM blower parameterization error 1. 516.00 ≤ P0 ≤ 516.01 2.
LME Series Technical Instructions Document No. LME-1000 Other Common Faults Known Causes of Loc 10 Loc 10 is a catchall fault that can be caused by a variety of issues. All known causes of Loc 10 are listed below in Table 7-1. Table 7-1: All Known Causes of Loc 10 Cause # LME71/73/75...
Page 92
Technical Instructions LME Series Document No. LME-1000 LME7 LED is Flashing Red When the LED on the front of the LME7 is flashing red very quickly, this indicates that the LME7 has been placed into Diagnostic Mode. While being in Diagnostic Mode does not prevent successful operation of the burner, it does remove the status that is typically displayed by the LED, as well as causes operators to incorrectly conclude that the LME7 is damaged.
LME Series Technical Instructions Document No. LME-1000 Modbus RTU and BACnet MS/TP Communication Introduction The physical connection from the LME7 burner control to the Modbus RTU or BACnet MS/TP system is made via an external OCI417.10 interface module. The OCI417.10 is compatible with all LME7…...
Technical Instructions LME Series Document No. LME-1000 Connection to the BMS The connection from the BMS to the OCI417.10 is via terminal block. The physical medium is RS-485. Multiple RS-485 nodes may be connected in a daisy-chain. For long runs (typically greater than 1,000 feet) or noisy environments, termination may be required on the end node.
LME Series Technical Instructions Document No. LME-1000 Using the OCI417 Configuration Utility 1. To download the OCI417 configuration utility, go to the following website and click the “OCI417.10 Configuration Utility” link to download and install the software. http://www.scccombustion.com/flame.htm. 2. Once installed, double-click the icon to open the configuration utility. 3.
Page 100
Technical Instructions LME Series Document No. LME-1000 4. Use a mini-USB cable to connect the OCI417.10 to the computer, such as SCC part number AGA5-05M. A driver may self-install the first time a connection is made. The connected device will then be indicated on the screen. 5.
LME Series Technical Instructions Document No. LME-1000 Updating the OCI417.10 Firmware 1. From the OCI417.10 Configuration Utility, click File -> Update Device… 2. Locate the supplied update file with a .duf extension and click Open. 3. The device will automatically reboot and reconnect with the OCI417.10 Configuration Utility once the firmware update is complete.
Technical Instructions LME Series Document No. LME-1000 Modbus Mapping ADDRESS ACCESS DESCRIPTION FORMAT NOTES PHASE Unsigned Int 16 FLAME INTENSITY Unsigned Int 16 MAINS VOLTAGE Unsigned Int 16 STARTUPS RESETTABLE Unsigned Int 32 STARTUPS TOTAL Unsigned Int 32 RELAY K12 CYCLES Unsigned Int 32 RELAY K11 CYCLES Unsigned Int 32...
Page 103
LME Series Technical Instructions Document No. LME-1000 Modbus Mapping ADDRESS ACCESS DESCRIPTION FORMAT NOTES 27 bit 2 INCREASE MODULATION (LR-OPEN) Boolean TERMINAL X5.03.3 27 bit 3 DECREASE MODULATION (LR-CLOSED) Boolean TERMINAL X5.03.2 27 bit 4 COMBUSTION AIR SWITCH (LP) Boolean TERMINAL X3.02.1 27 bit 5 LOW GAS PRESSURE SWITCH (Pmin)
Page 104
Technical Instructions LME Series Document No. LME-1000 Modbus Mapping ADDRESS ACCESS DESCRIPTION FORMAT NOTES HISTORY 7 ERROR LOAD Unsigned Int 16 255 IS NO LOAD RECORDED HISTORY 8 ERROR CODE Unsigned Int 16 HISTORY 8 ERROR STARTUPS Unsigned Int 32 HISTORY 8 ERROR PHASE Unsigned Int 32 PHASE IS 0 WHEN NO ERROR...
LME Series Technical Instructions Document No. LME-1000 BACnet Mapping ADDRESS DESCRIPTION UNITS ACTIVE TEXT INACTIVE TEXT PHASE NO UNITS FLAME INTENSITY PERCENT MAINS VOLTAGE VOLTS STARTUPS RESETTABLE NO UNITS STARTUPS TOTAL NO UNITS RELAY K12 CYCLES NO UNITS RELAY K11 CYCLES NO UNITS RELAY K2 CYCLES NO UNITS...
Page 106
Technical Instructions LME Series Document No. LME-1000 BACnet Mapping ADDRESS DESCRIPTION UNITS ACTIVE TEXT INACTIVE TEXT AV46 HISTORY 6 ERROR LOAD PERCENT AV47 HISTORY 7 ERROR CODE NO UNITS AV48 HISTORY 7 ERROR STARTUPS NO UNITS AV49 HISTORY 7 ERROR PHASE NO UNITS AV50 HISTORY 7 ERROR LOAD...
LME Series Technical Instructions Document No. LME-1000 BACnet Mapping ADDRESS DESCRIPTION UNITS ACTIVE TEXT INACTIVE TEXT BV27 FAN (M) CMD ON CMD OFF BV28 VALVE 1 (V1) CMD ON CMD OFF BV29 VALVE 2 (V2) CMD ON CMD OFF Unused Inputs Any inputs unused by the selected PME…...
Page 108
Technical Instructions LME Series Document No. LME-1000 Intentionally Left Blank Section 8 Page 14 SCC Inc.
LME Series Technical Instructions Document No. LME-1000 ACS410 Software Introduction The LME7 burner control can be completely programmed using either the AZL23 or a PC with the ACS410 software. Most people find that using the AZL23 is more convenient than the ACS410 for a “manual”...
Accept the license agreement and click “Next”. d. Select the folder where the ACS410 software will be installed. The default folder is C:\Program Files (x86)\Siemens\ACS410. Click “Next”. e. Select the folder where the ACS410 software shortcuts will be installed in the Start Menu.
LME Series Technical Instructions Document No. LME-1000 Connecting to a PC The following steps summarize the procedure for establishing communication between the LME7 and a PC. 1. An OCI410 interface module is required to connect the LME7 to a PC. Three different interface modules are available: Table 9-1: Available Interface Modules to Connect the LME7 to a PC Interface Module...
The default location for storing parameter sets is C:\Program Files (x86)\Siemens\ACS410\bkp. Notice that two files are created in this folder: one with a .bkp file extension and one with a .unl file extension. Both files are necessary in order to view the parameter set or restore it to an LME7.
LME Series Technical Instructions Document No. LME-1000 Uploading a Parameter Set to an LME7 The following steps outline the procedure for uploading parameter sets from a PC to an LME7. 1. Ensure that the ACS410 software is open, and the PC is connected to the LME7 at the service or OEM level.
Technical Instructions LME Series Document No. LME-1000 Creating an LME7 Startup Report The following steps outline the procedure for saving, viewing, and printing a startup report to a 1. Open the ACS410 software. Instead of logging in, click the “Offline” button. Then click the “Backup”...
LME Series Technical Instructions Document No. LME-1000 Synchronizing the LME7 and PME Parameters The ACS410 software can be used to synchronize the parameter set used by the LME7 and the backup copy stored on the PME chip. 1. Ensure that the ACS410 software is open, and the PC is connected to the LME7 at the service or OEM level.
Technical Instructions LME Series Document No. LME-1000 Saving and Viewing Trends The ACS410 software can be used to view and save trends. Trending enables a technician to easily view and quantify system behavior over time. The following steps outline the procedure for viewing and saving trends with the ACS410 software.
Page 119
5. Trending data is stored in the following location: C:\Program Files (x86)\Siemens\ACS410\tn. Each set of trending data creates two files: one with a .unl format and one with a .dtd format. Both files are necessary if the trend is to be viewed at a later time through the ACS410 software.
Technical Instructions LME Series Document No. LME-1000 Viewing the Status Screen When connected to the LME7, the ACS410 can provide a status screen. This provides a useful summary of the LME7 inputs and outputs, as well as the operating state of the LME7. The following steps outline the procedure for viewing the ACS410 status screen.
Page 123
LME Series Technical Instructions Document No. LME-1000 Appendix A: LME7 Application Guide Description The LME7 Application Guide includes programming, wiring, and operation examples of the control system for the most common applications. SCC Inc. Page 1 Appendix A...
Technical Instructions LME Series Document No. LME-1000 Table of Contents Honeywell Modutrol IV Motor with the LME75 Introduction ........................... 3 Setup Procedure without Valve Proving ................. 3 Sequence of Operation without Valve Proving ............... 5 Setup Procedure with Valve Proving ..................7 Sequence of Operation with Valve Proving ................
Page 125
Honeywell Modutrol IV with the LME75 Introduction The Siemens LME75 burner control is designed specifically for use with a Siemens SQM4… or SQM5… series actuator. However, with some simple programming changes and the addition of only a few relays, the LME75 can be set up to safely and effectively control a Honeywell Modutrol IV motor.
Page 126
Technical Instructions LME Series Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) Figure A-1: Wiring a Honeywell Mod IV Motor to the LME75 (no Valve Proving) Appendix A Page 4 SCC Inc.
Page 127
LME Series Technical Instructions Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) Sequence of Operation without Valve Proving 1. The LME75 is in standby. All valves are closed and all relays are de-energized. All relay contacts are as shown in the electrical schematic. The Honeywell Modutrol IV motor (hereafter referred to as mod motor) is at the low fire position.
Page 128
Technical Instructions LME Series Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) 7. Main valve output X7-04.4 is energized in phase 50 (for piloted burners) or phase 40 (for non-piloted burners). Input X5-03.3 is energized, which has no effect. Output X2-09.3 is de-energized, so normally open contact CR-1B remains open, and relay CR-2 remains de- energized.
Page 129
LME Series Technical Instructions Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) Setup Procedure with Valve Proving 1. The following procedure should be used when valve proving is being utilized. 2. Set the following parameters in the LME75 as described below: Parameter 241 = 1 Parameter 259 = Greater than or equal to the running time of the Honeywell Modutrol IV motor being used...
Page 130
Technical Instructions LME Series Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) Figure A-2: Wiring a Honeywell Mod IV Motor to the LME75 (with Valve Proving) Appendix A Page 8 SCC Inc.
Page 131
LME Series Technical Instructions Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) Sequence of Operation with Valve Proving 1. The LME75 is in standby. All valves are closed and all relays are de-energized. All relay contacts are as shown in the electrical schematic. The Honeywell Modutrol IV motor (hereafter referred to as mod motor) is at the low fire position.
Page 132
Technical Instructions LME Series Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) 5. Output X2-09.3 de-energizes and output X2-09.2 energizes in phase 36. These actions de-energize relay CR-1 and energize relay CR-3. Normally open contact CR-1A opens, removing the connection that was keeping the mod motor to high fire. Since normally open contact CR-2 remains open, the mod motor drives to the low fire position.
Page 133
LME Series Technical Instructions Document No. LME-1000 Honeywell Modutrol IV with the LME75 (continued) 11. Output X2-09.1 is energized in phase 10 to drive the mod motor to low fire. Since the mod motor is already at the low fire position, the low fire proving switch is closed, and actuator feedback input X2-09.4 is energized.
Page 134
Technical Instructions LME Series LME-1000 PME75.811A1 Phase Diagram with Relays Phase Param. STARTUP OPERATION SHUTDOWN VALVE PROVING SAFETY Terminal Description Notes TIME 1 X3-04.5 Main Voltage X3-04.1 Safety Loop X5-03.1 Burner On X3-02.1 Air Pressure Switch Note 3 X5-01.2 Gas Pressure Switch(es) Note 4 X9-04.2 Valve Proving Pressure Switch...
LME Series Technical Instructions Document No. LME-1000 Two Flame Detectors Introduction When using a piloted line burner with a flame propagating in excess of three feet, two flame detectors are required by both NFPA 86 and CSA B149.3. These flame detectors are: 1.
Page 136
Technical Instructions LME Series Document No. LME-1000 Two Flame Detectors (continued) Wiring Diagrams Two Flame Rods (Any LME7) Two Flame Scanners (LME71/73) Appendix A Page 14 SCC Inc.
Page 137
LME Series Technical Instructions Document No. LME-1000 Two Flame Detectors (continued) Two Flame Scanners (LME75) One Flame Rod and One Flame Scanner (LME71/73) SCC Inc. Page 15 Appendix A...
Page 138
Technical Instructions LME Series Document No. LME-1000 Two Flame Detectors (continued) One Flame Rod and One Flame Scanner (LME75) Appendix A Page 16 SCC Inc.