A.2 Examples of acceptance tests
3. Select SS1
4. Deselect SS1
You have completed the acceptance test of the SS1 function.
388
3.1. Select SS1 while the motor is switched on.
Test each configured activation, e.g. via digital inputs and PROFIsafe.
3.2. In your machine, check the following:
● The motor brakes on the OFF3 ramp.
● SS1 is active (r9773.6 = 1).
● After the p9652 time has expired, the inverter signals: "STO is active"
(r9773.1 = 1).
4.1. Deselect SS1.
4.2. Check the following:
● SS1 is not active (r9773.6 = 0).
● The inverter signals neither faults nor alarms of the safety functions
(r0945[0...7], r2122[0...7]).