Siemens Sinamics G120 Function Manual page 111

Safety integrated
Hide thumbs Also See for Sinamics G120:
Table of Contents
You have reset the password for the safety functions.
Parameter
p0010 = 95
p9761
p9762
p9763
p9701 = DC
hex
p0010 = 0
p0971 = 1
Safety Integrated - SINAMICS G110M, G120, G120C, G120D and SIMATIC ET 200pro FC-2
Function Manual, 01/2017, FW V4.7 SP6, A5E34261271B AD
Description
Drive commissioning parameter filter
Safety Integrated commissioning
Enter a password (factory setting: 0000 hex)
Permissible passwords lie in the range 1 ... FFFF FFFF.
New password
Confirm password
Confirm data change (factory setting: 0)
Confirm the SI basic parameter change.
Drive commissioning parameter filter
0: Ready
Save parameter
1: Save the drive object (copy from RAM to ROM)
After the inverter has saved the parameters in a non-volatile fashion, then p0971 = 0.
5.7 Resetting the password for the safety functions
Commissioning
111