Non-Reversing Starter (Network & Local I/O); Two-Wire Control - Allen-Bradley E200 User Manual

Electronic overload relay/parameter configuration module
Table of Contents
Chapter 4
Operating Modes
68
Figure 26 - Non-reversing Starter (Network & Operator Station) with Feedback Wiring Diagram
Run Aux
I-Run
DeviceLogix Program
The DeviceLogix program is automatically loaded and enabled in the E200 relay on
power-up or when Operating Mode (Parameter 195) is set to a value of 12.
Non-reversing Starter (Network & Local I/O) – Two-wire Control
Operating Mode Non-Reversing Starter (Network & Local I/O) – Two Wire Control
(Parameter 195 = 16) uses the network tag LogicDefinedPt00Data in Output
Assembly 144 in Remote control mode and Input 0 in Local control mode to control
Relay 0, which controls the contactor coil. Input 1 determines whether the motor
starter is in Remote or Local control mode. LogicDefinedPt00Data is a maintained
value, so the non-reversing starter remains energized when LogicDefinedPt00Data has
a value of 1 in Remote control mode. Program the appropriate state of the starter by
using the Network Communication Fault and Network Communication Idle
parameters (Parameters 569 – 573) described in
In Local control mode, the state of Input 0 controls Output Relay 0, which controls the
contactor coil. Input 0 is a maintained value, so the non-reversing starter remains
energized when Input 0 is active.
Use Input 1 to select between Local and Remote control mode. Activate Input 1 to
select Remote control mode. De-activate Input 1 to select Local control mode.
The reset button of the E200 Operator Station is enabled for this operating mode.
Rules
1. Output Pt00 Assignment (Parameter 202) must be set to Control Relay.
2. Overload Trip must be enabled in TripEnableI (Parameter 183).
3. Communication Fault & Idle Override (Parameter 346) must be enabled.
4. Network Fault Override (Parameter 347) must be enabled.
Rockwell Automation Publication 193-UM017A-EN-P - April 2019