Module Status (Ms) - Allen-Bradley E300 User Manual

Electronic overload relay
Hide thumbs Also See for E300:
Table of Contents
Chapter 12
Troubleshooting
LED Color
State
The E300 EtherNet/IP Communication Module is
None
not receiving power.
Green, Red, Not
Flashing (once) Normal
Illuminated
The E300 EtherNet/IP Communication Module is
Green
Flashing
not being scanned by the EtherNet/IP master.
Normal operating state, the E300 EtherNet/IP
Green
Solid
Communication Module is allocated to its master. No action is required.
One or more EtherNet/IP connections timed out. Reset the E300 EtherNet/IP Communication Module.
Red
Flashing
The E300 Overload Relay is in a fault state.
Red
Solid
Diagnostics test failed on power-up/reset.
LED Color
State
The E300 DeviceNet Communication Module is
None
not receiving power.
Green, Red, Not
Flashing (once) Normal
Illuminated
Green
Flashing
Normal (Program / Non-Run Mode)
Green
Solid
Normal (Run Mode)
Red
Flashing
Recoverable Fault State
Red
Solid
Unrecoverable Fault State.
208

Module Status (MS)

Table 46
explains the states of the Module Status (MS) LED of the E300 EtherNet/IP
Communication Module.
Table 46 - EtherNet/IP Communication Module Status Troubleshooting
Possible Cause
Check the control power connection on the A1 and A2 terminals of the
E300 Control Module.
This is a normal power-up sequence.
Check the Ethernet scan list for the correct scanner configuration.
Reset the E300 EtherNet/IP Communication Module or verify the validity of the data in the
configuration assembly.
Cycle power to the device. If the fault still exists, replace the device.
Table 47
explains the states of the Module Status (MS) LED of the E300 DeviceNet
Communication Module.
Table 47 - DeviceNet Communication Module Status Troubleshooting
Possible Cause
Check the DeviceNet control power on the A1 and A2 terminals of the E300 Control
Module.
This is a normal power-up sequence.
The E300 Module is in Program/Non-run Mode where no I/O connection exists or an I/O
connection exists while not in Run Mode.
The E300 Module is in Run Mode where I/O connection(s) is in Run State.
The E300 Module has been mis-configured and results in a fault condition.
The E300 Module has become inoperable due to a defective and/or intermittent
component within the unit. In most instances, activating the Trip/Reset button will not
remove this fault condition and the only way to recover from this condition is to replace
the E300 module or identify/replace the faulty component(s). In some scenarios, pressing
the Trip/Reset button may clear this fault condition. In this case, the cause for the fault is
most likely to be environmentally related and therefore component replacement is not
required.
Rockwell Automation Publication 193-UM015F-EN-P - August 2018
Corrective Action
Corrective Action
Table of Contents
loading

Table of Contents