Monitor Operating Mode - Allen-Bradley E300 User Manual

Electronic overload relay
Hide thumbs Also See for E300:
Table of Contents

Monitor Operating Mode

Rules
1. Available for Control Module firmware v5.000 and higher.
2. Set two of the Output Ptxx Assignments (Parameters 202...204) to Control
Relay.
3. Overload Trip must be enabled in TripEnableI (Parameter 183).
Wiring Diagram
Figure 74
is a wiring diagram of a Two-speed Starter with Output Relay 0 and Output
Relay 1 configured as control relays. Both Output Relay 0 and Output Relay 1 go to an
open state when there is a trip event.
Figure 74 - Two-Speed Starter (Custom) Wiring Diagram
DeviceLogix Program
The last saved DeviceLogix program is executed in the E300 relay on power-up or
when Operating Mode (Parameter 195) is set to a value of 53.
Timing Diagram
Figure 75 - Two-Speed Starter (Custom) Timing Diagram
Trip Relay
Device Status 0
Trip Preset
Trip Reset
The E300 relay's monitor-based operating mode allows you to disable all protection
features of the E300 relay. You can use the E300 relay as a monitoring device to report
current, voltage, power, and energy information.
There is one monitor based operating mode – Custom.