Taps - Allen-Bradley Guardmaster GuardLink User Manual

Safety system
Table of Contents
Chapter 1
Overview

Taps

12
Figure 1 - Typical GuardLink System
Each DG safety relay can accommodate
up to two GuardLink circuits, each
containing up to 32 devices.
One DG
safety relay
Single Wire Safety for Expansion
R R
Output monitoring
One optional Ethernet interface
(Required if guard locking is used)
Taps create nodes in the GuardLink circuit. A safety device is connected to
each tap. Two types of taps are available:
• Taps that interface with devices having voltage-free safety contacts
• Taps that interface with devices that have OSSD signals
Each type is available in an 8-pin and 5-pin device connection version.
The taps are intended to be mounted on the machine, near the location of the
device it monitors. The different types and versions can be connected in any
order and can be mixed.
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018
One GuardLink tap for each
safety device.
One terminator for each
GuardLink circuit.
Cordsets and patchcords
Table of Contents
loading

Table of Contents