Motor control and I/O board (RMIO)

What this chapter contains

This chapter shows
• external control connections to the RMIO board for the ACS800 Standard Control
Program (Factory Macro)
• specifications of the inputs and outputs of the board.

Note on optional terminal block X2

The connections for the RMIO board shown below apply also to optional terminal
block X2 available for the ACS800-07. The terminals of the RMIO board are wired to
terminal block X2 internally.
Terminals of X2 accept cables from 0.5 to 4.0 mm
torque for screw terminals is 0.4 to 0.8 Nm (0.3 to 0.6 lbf ft). For disconnecting wires
from spring terminals, use a screw driver with a blade thickness of 0.6 mm
(0.024 in.) and width of 3.5 mm (0.138 in.), for example, PHOENIX CONTACT SZF
1-0,6X3,5.

Note on terminal labelling

Optional modules (Rxxx) may have identical terminal designations with the RMIO
board.