Single drive common dc configurations
Hide thumbs Also See for ACS800:

Quick Links

ACS800
Application Guide
ACS800 Single Drive Common DC Configurations
Table of Contents
loading

Summary of Contents for ABB ACS800

  • Page 1 ACS800 Application Guide ACS800 Single Drive Common DC Configurations...
  • Page 3 ACS800 Single Drive Common DC Configurations Application Guide 3AFE64786555 REV E EFFECTIVE: 03.12.2004  2004 ABB Oy. All Rights Reserved.
  • Page 5: Table Of Contents

    Table of contents Introduction Possible main supply connections Step by step guide Design Power limit ..............11 Fuses .
  • Page 7: Introduction

    Introduction Connecting the DC buses of frequency converters together results in energy savings and in some cases simplifies the connection to the main supply. With common DC the braking energy of one converter can be used for the other converters and motors.
  • Page 8: Possible Main Supply Connections

    Possible main supply connections Figure 1. Common DC connections. Cases a and b. R7 / R6 R7 / R5 Figure 2. Common DC connections. Cases c, d1 and d2. Cases b, c and d can be used when the total power taken from the main supply, , is smaller than the drive power rating, P , of the biggest converter.
  • Page 9 Note: With ACS800-11 only connection presented in case d1/d2 is allowed. Note: With ACS800-11 220 V units, the voltage drop over the charging resistor during charging can generate a permanent undervoltage fault. Contact your local...
  • Page 10: Step By Step Guide

    Step by step guide 1) Select the converters and preselect the main supply connection. See Possible main supply connections Appendix A Charging circuit capacity. 2) Check from Table 1 that the connection is possible. 3) Check by using equation 1 that the load does not exceed the total power limit of the system.
  • Page 11: Design

    The power correction factor, k, for each combination can be found from Table 1. When several converters are connected to the main supply, the least efficient power correction factor is chosen from table 1, i.e. the smallest factor. See Example1 Example2. Table 1 Power correction factors ACS800 R2-R3 R5-R6 R7-R8 R2-R3 k=0.5 k=0.7...
  • Page 12 Example1 The DC buses of three converters ACS800-0004-5, 2.2 kW, R2; ACS800-0025-5, 18.5 kW, R3 and ACS800-0025-5, 18.5 kW, R3 are connected together. The input terminals of the 2.2 kW converter are left unconnected. According to Table 1, k = 0.5 when two R3´s are connected to the main supply, therefore P...
  • Page 13: Fuses

    Because of the complicated fault current paths the selectivity of the fuses cannot be guaranteed in all conditions. aR fuses must be installed on both DC wires. Table 2 Recommended DC side aR fuses. ACS800-01/04/11 Frame size 230 V 400 V...
  • Page 14: Cables

    Cables • Select the input power cables as described in the appropriate drive Hardware Manual. The cross-sectional area of the DC cables must be the same as the cross-sectional area of the AC side cables. • If screened DC cables are used, ground the screen at the other end only. •...
  • Page 15: Allowed Braking Power And Need For A Brake Resistor

    Allowed braking power and need for a brake resistor 1. For each drive check that the braking power does not exceed the allowed braking power. See Calculation of the allowed braking power below. 2. For the common DC system check whether it needs to be equipped with an additional brake chopper and resistor.
  • Page 16: Calculation Of The Allowed Braking Power

    Calculation of the allowed braking power If drive is not connected to the main supply, ensure that the braking power meets condition 1 below. If drive is connected to the main supply, ensure the braking power meets condition 1 AND condition 2 below. Condition 1 The drive braking power may not exceed the drive power rating.
  • Page 17 The DC buses of three converters ACS800-0140-5, 110 kW, R6; ACS800-0140-5, 110 kW, R6, and ACS800-0070-5, 55 kW, R5 are connected together. Only one 110 kW converter is connected to the main supply. The duty cycle is shown in the table below.
  • Page 18: Internal Brake Chopper

    Internal brake chopper • Only one internal brake chopper is allowed to be active. • If an internal chopper is used, it must be in the biggest converter. • The maximum braking power of the brake chopper or the inverter must not be exceeded.
  • Page 19 Peak current through the contactor in brake resistor circuit can be calculated with equation 5. ⋅ 1.21 U I ˆ ------------------------- (equation 5) brake The rms current during the braking can be calculated with equation 6. (equation 6) ------------- brake is the brake resistor‘s resistance.
  • Page 20: Wiring

    Wiring Supply Use the same supply connection point. All converters must be fed from the same transformer. The supply impedance is an important parameter, which influences the current distribution. All converters must have equal supply impedance. Powering the AC fans in R7 and R8 Appendix B Powering the AC fans of R7 and R8 for more information.
  • Page 21 ACS 800 2 2 R + 2 2 1 2 2 2 230 V~ θ 2 2 3 2 2 R - θ +24V 2 2 8 2 2 9 2 2 1 0 DIIL 2 2 1 1 2 2 1 2 2 2 230 V~ 2 2 3...
  • Page 22: Phase Loss Guard

    Phase loss guard It is recommended to use phase loss guard in the input supplies of all of the converters. If phase loss guard is not used and the fuse of one of the input supply phases blows, the semiconductors of the converters may be overloaded and damaged.
  • Page 23 Figure 4. READY signal wiring example. Wiring...
  • Page 24: Start-Up

    Always check the setting of parameter 16.15 I/O START MODE after software update, macro change or control board replacement! See ACS800-11 Hardware Manual for information on how to change the line-side converter parameters with control panel. Start-up...
  • Page 25: Appendix A Charging Circuit Capacity

    Appendix A Charging circuit capacity The total power of the common DC system P is higher if the smallest converter out.tot is not connected directly to the main supply. To determine whether it is possible to leave some converters unconnected, the total charging energy of the DC capacitors and associated inrush currents must be analysed.
  • Page 26 5700uF 10800uF 1.35 500V 4829J Even if the charging resistor of the ACS800-0260-5 (R7) is able to withstand the whole charging energy, E = 4829 J < E = 5600 J, the biggest converter ACS800-0400-5 (R8) is connected to the main supply.
  • Page 27 Example 6 The DC buses of two ACS800-0120-5 (R6) and four ACS800-0260-5 (R7) are connected together. The main supply voltage is 500 V. The total charging energy of the DC link capacitors is 6 – ⋅ ⋅ ⋅ ⋅ ⋅...
  • Page 28 Table 3 Capacitances of the DC link capacitor. Frame size ACS800-x1 ACS800-x1 ACS800-x1 / uF 0001-2 0003-3 0004-5 0002-2 0004-3 0005-5 0003-2 0005-3 0006-5 0004-2 0006-3 0009-5 0005-2 0009-3 0011-5 0006-2 0011-3 0016-5 0009-2 0016-3 0020-5 0011-2 0020-3 0025-5 0023-3...
  • Page 29 Frame size ACS800-x2/x4 ACS800-x2/x4 ACS800-x2/x4 / uF 0080-2 0140-3 0170-5 5700 0100-2 0170-3 0210-5 5700 0120-2 0210-3 0260-5 5700 0140-2 0260-3 0270-5 8600 0170-2 0300-5 8600 0320-5 8600 0210-2 0320-3 0400-5 10800 0230-2 0400-3 0440-5 12900 0490-5 12900 0260-2 0440-3...
  • Page 30: Appendix B Powering The Ac Fans Of R7 And R8

    Appendix B Powering the AC fans of R7 and R8 If the supply of frame size R7 or R8 is not connected to the main supply, the AC fan must be powered separately. Feed the primary of the fan circuit transformer with the converter’s nominal main supply voltage, V- and W-phases, via the built-in fan circuit.