(1) Signal output when the constant-speed frequency is reached (01: FA1)
The inverter outputs the signal when the output frequency reaches the frequency specified by a frequency
setting (F001, A020, A220) or multispeed setting (A021 to A027).
f
on
Output frequency
FA1
(2) Signal output when the set frequency is exceeded (02: FA2)
The inverter outputs the signal when the output frequency exceeds the acceleration or deceleration
frequency specified by a frequency setting ("C042" or "C043" [FA2]).
C042
f
on
Output frequency
FA2
(3) Signal output only when the set frequency is reached (06: FA3)
The inverter outputs the signal only when the output frequency reaches the frequency specified by a
frequency setting ("C042" or "C043" [FA3]).
Output frequency
C042
f
on
FA3
f
off
C043
f
f
C043
on
f
off
7 - 69
Chapter 7 Explanation of Functions
Set frequency
(Example)
Maximum frequency (fmax) = 120 Hz
Set frequency (fset) = 60 Hz
fon = 120 x 0.01 = 1.2 (Hz)
foff = 120 x 0.02 = 2.4 (Hz)
At acceleration, the signal turns on when the output
frequency reaches 58.8 Hz (60 - 1.2 = 58.8).
At deceleration, the signal turns off when the output
frequency reaches 57.6 Hz (60 - 2.4 = 57.6).
fon: 1% of maximum frequency
off
foff: 2% of maximum frequency
fon: 1% of maximum frequency
foff: 2% of maximum frequency
f
off
fon: 1% of maximum frequency
foff: 2% of maximum frequency