Wiring Connections - ABB ACS 601 Hardware Manual

Ac drives, 3 to 150 hp, 2.2 to 110 kw
Hide thumbs Also See for ACS 601:
Table of Contents
Encoder Cable (ACP 600)
Control Panel Cable

Wiring Connections

ACS/ACC/ACP 601 Drives
a
A double shielded twisted
pair cable
The analog and digital input signals should be run in separate, shielded
cables.
Relay-controlled signals, providing their voltage does not exceed 48 V,
can be run in the same cables as digital input signals. It is
recommended that the relay-controlled signals be run as twisted pairs.
Never mix 24 VDC and 115 / 230 VAC signals in the same cable.
2
Min. 4 x 0.25 mm
(#22 AWG) + 2 x 0.5 mm
shielded twisted multipair cable, optical coverage > 91 %. The
maximum cable length is 150 m (500 ft.). Suitable cable
recommendation is available from ABB.
In remote use the cable connecting the Control Panel to the ACx 600
must not exceed 3 meters (10 ft). The cable type tested and approved
by ABB is provided in Control Panel option kits.
WARNING! This work should only be carried out by a qualified
electrician. The Safety Instructions on the first pages of this manual
must be followed. Negligence of these instructions can cause injury or
death.
The input power and motor cables connect to the terminal block of the
ACx 601 in the lower part of the frame. The control cables pass in front
of the power terminals to the NIOC/NIOCP board.
To connect the input power, motor and control cables carry out the
following procedure.
WARNING! Make sure that the ACx 601 is disconnected from the
power network during installation. If the ACx 601 is already connected
to the power, wait for 5 minutes after disconnecting power.
Chapter 3 – Electrical Installation
b
A single shielded twisted
multipair cable
2
(#20AWG) min. single
ACx=ACS/ACC/ACP
3-5

Hide quick links:

Table of Contents
loading

This manual is also suitable for:

Acc 601Acp 601Acs 600

Table of Contents