ABB ACS 600 Installation Manuals

ABB ACS 600 Installation Manuals

Hide thumbs Also See for ACS 600:

Quick Links

ACS 600
CHECK BOX CONTENTS: ACx 601, Manual(s), Testing report, Ordered options, Quick Guide(s)
CHECK INSTALLATION SITE AMBIENT CONDITIONS: See Manual.
CHECK INSTALLATION SPACE: ACx 600 free space requirements are 300 mm above and below, 50 mm on the left and on the right.
CHECK INSTALLATION SURFACE: Vertical, smooth and solid, free from heat, damp and condensation.
CHECK ACCESSORIES NEEDED: See Manual for fuse, supply disconnecting device and cable specifications.
ENSURE MAINS SUPPLY TO INSTALLATION IS OFF.
LOCK THE DISCONNECTOR TO OPEN POSITION.
ACx 600 MUST BE INSTALLED BY A COMPETENT PERSON.
IF IN DOUBT DO NOT INSTALL.
1
2.
1. Measure the places for four screw holes.
Mark the hole positions. 2. Drill the holes.
3. Screw in the screws.
4
STOP
FOR
INSTALLATION
OF OPTIONAL
EQUIPMENT, SEE
SEPARATE
INSTRUCTIONS
INCLUDED IN
THE DELIVERY.
1. Strip off the insulation from the motor cable
and mains cable. Twist the screen wires into
bundles. 2. Make suitable holes to motor and
mains cable grommets.
Before Starting Installation
6-7
1.
15
3.
Position ACx 600 onto screws and securely
tighten in all four corners. Note: Lift ACx 600
by its chassis, not by its cover.
5
1.
2.
ACS/ACC/ACP 601-0005-3 ... -0016-3,
-0006-5 ... -0020-5 and -0009-6 ... -0020-6
2
10
6-7
1. Undo the two screws. 2. Lift the lower edge
of the cover. 3. Disconnect the cable from
connector X2. Remove the cover.
6
INPUT
300 mm
free space
Mains cable
Lead the motor and mains cables through the
bottom plate.
Installation Guide
3
X2
3.
1.
2.
STOP
OUTPUT
CHECK THE
INSULATIONS
OF MOTOR,
AND MAINS
AND MOTOR
Motor
CABLE.
cable
See Manual.
7
loading

Summary of Contents for ABB ACS 600

  • Page 1 ACS 600 Installation Guide ACS/ACC/ACP 601-0005-3 ... -0016-3, -0006-5 ... -0020-5 and -0009-6 ... -0020-6 Before Starting Installation CHECK BOX CONTENTS: ACx 601, Manual(s), Testing report, Ordered options, Quick Guide(s) CHECK INSTALLATION SITE AMBIENT CONDITIONS: See Manual. CHECK INSTALLATION SPACE: ACx 600 free space requirements are 300 mm above and below, 50 mm on the left and on the right.