Product Failure Rates (Failures Per Hour) - Allen-Bradley 1734-IB8S User Manual

Point guard i/o safety modules
Hide thumbs Also See for 1734-IB8S:
Table of Contents
Product Failure Rates
(failures per hour)
Table 21 - Product Failure Rates (failures per hour)
Catalog Number
Series
1734-IB8S
B
1734-OB8S
B
1734-IE4S
A
1734-IB8S
B
1734-OB8S
B
1734-OBV2S
B
1734-IE4S
A
(1) These failure rates assume that the module is represented by one block in a reliability block diagram. The single channel rates must
be applied to the reliability block if the module is configured in Single Channel mode. The dual channel rates must be applied to the
reliability block if the module is configured in Dual Channel mode.
(2) 1734-OB8S single channel mode is only certified for functional safety applications with Process Safety Times ≥ 600 msec or with
Demand Rates ≤ 1 Demand per Minute.
All 1734-IB8S safety input channels, all 1734-OB8S safety output channels, and
all 1734-OBV2S safety output channels must utilize pulse testing when used in
single channel functional safety applications
Rockwell Automation Publication 1734-UM013N-EN-P - September 2017
(1)
λ
Module I/O
S
Configuration
Single Channel Inputs
2.56E-07
(2)
(2)
Single Channel Outputs
2.52E-07
Single Channel Inputs
4.23E-07
Dual Channel Inputs
2.96E-07
Dual Channel Outputs
2.95E-07
Dual Channel Outputs
4.08E-07
Dual Channel Inputs
6.56E-07
Safety Data
Appendix D
λ
λ
DD
DU
2.55E-07
6.02E-10
(2)
(2)
2.52E-07
4.47E-09
4.23E-07
1.01E-10
2.94E-07
1.84E-10
2.95E-07
1.84E-10
4.08E-07
2.41E-10
6.56E-07
6.67E-11
209