Emerson Unidrive M200 Control Quick Start Manual page 38

Flexible machine integration through communications
Hide thumbs Also See for Unidrive M200:
Table of Contents
00.043 {11.025}
RW
Txt
300 (0), 600 (1), 1200 (2),
OL
2400 (3), 4800 (4), 9600 (5),
RFC-A
Defines the serial baud rate of the drive
Changing the parameters does not immediately change the serial communications settings. See
Reset Serial Communications (00.045) for more details.
00.044 {11.023}
RW
Num
OL
RFC-A
Used to define the unique address for the drive for the serial interface. The drive is always a slave
address 0 is used to globally address all slaves, and so this address should not be set in this
parameter.
Changing the parameters does not immediately change the serial communications settings. See
Reset Serial Communications (00.045) for more details.
00.045 {11.020}
RW
Bit
OL
RFC-A
Set to On (1) to update communications set-up.
The display will briefly display On and return to Off on reset.
NOTE
00.046 {12.042}
RW
Num
OL
RFC-A
Defines the upper current threshold for the brake. See Brake Controller Brake Release in Drive User
Guide.
38
Serial Baud Rate
19200 (6), 38400 (7),
57600 (8), 76800 (9),
115200 (10)
Serial Address
1 to 247
Reset Serial Communications
Off (0) or On (1)
Brake Controller Upper Current Threshold
0 to 200 %
19200 (6)
ND
NC
Off (0)
50 %
Unidrive M200/201 Control Quick Start Guide
US
US
1
US
US
Issue Number: 2