Enclosure Design And Drive Ambient Temperature; Figure 3-34 Enclosure Having Front, Sides And Top Panels Free To Dissipate Heat - Emerson unidrive sp User Manual

Universal variable speed ac drive for induction and servo motors model sizes 0 to 6
Hide thumbs Also See for unidrive sp:
Table of Contents
Safety
Product
Mechanical
Information
Information
Installation
Dissipation of each drive: 187 W (see Table 12-4 Losses @ 40°C
(104°F) ambient on page 268)
Dissipation of each external EMC filter: 9.2 W (max) (see section
12.2.1 EMC filter ratings on page 280)
Total dissipation: 2 x (187 + 9.2) =392.4 W
The enclosure is to be made from painted 2 mm (0.079 in) sheet steel
having a heat transmission coefficient of 5.5 W/m
front, and two sides of the enclosure are free to dissipate heat.
2
The value of 5.5 W/m
/ºC can generally be used with a sheet steel
enclosure (exact values can be obtained by the supplier of the material).
If in any doubt, allow for a greater margin in the temperature rise.
Figure 3-34 Enclosure having front, sides and top panels free to
dissipate heat
H
W
Insert the following values:
T
40°C
int
T
30°C
ext
k
5.5
P
392.4 W
The minimum required heat conducting area is then:
392.4
-------------------------------- -
A
=
e
(
)
5.5 40 30
2
2
= 7.135 m
(77.8 ft
) (1 m
Estimate two of the enclosure dimensions - the height (H) and depth (D),
for instance. Calculate the width (W) from:
A
2HD
e
W
------------------------- -
=
H
+
D
Inserting H = 2m and D = 0.6m, obtain the minimum width:
(
×
×
7.135
2
2
0.6
---------------------------------------------------- -
W
=
2
+
0.6
=1.821 m (71.7 in)
If the enclosure is too large for the space available, it can be made
smaller only by attending to one or all of the following:
Using a lower PWM switching frequency to reduce the dissipation in
the drives
Reducing the ambient temperature outside the enclosure, and/or
applying forced-air cooling to the outside of the enclosure
Reducing the number of drives in the enclosure
Removing other heat-generating equipment
Calculating the air-flow in a ventilated enclosure
The dimensions of the enclosure are required only for accommodating
the equipment. The equipment is cooled by the forced air flow.
Calculate the minimum required volume of ventilating air from:
3kP
-------------------------- -
V
=
T
T
int
ext
Unidrive SP User Guide
Issue Number: 13
Electrical
Getting
Basic
installation
Started
parameters
the motor
2
o
/
C. Only the top,
D
2
2
= 10.9 ft
)
)
www.controltechniques.com
Running
SMARTCARD
Optimization
operation
Where:
V
Air-flow in m
Maximum expected temperature in °C outside the
T
ext
enclosure
Maximum permissible temperature in °C inside the
T
int
enclosure
P
Power in Watts dissipated by all heat sources in the
enclosure
k
Ratio of
Where:
P
is the air pressure at sea level
0
P
is the air pressure at the installation
I
Typically use a factor of 1.2 to 1.3, to allow also for pressure-drops in
dirty air-filters.
Example
To calculate the size of an enclosure for the following:
Three SP1403 models operating at the Normal Duty rating
Each drive to operate at 6kHz PWM switching frequency
Schaffner 10A (4200-6118) external EMC filter for each drive
Braking resistors are to be mounted outside the enclosure
Maximum ambient temperature inside the enclosure: 40°C
Maximum ambient temperature outside the enclosure: 30°C
Dissipation of each drive: 101 W
Dissipation of each external EMC filter: 6.9 W (max)
Total dissipation: 3 x (101 + 6.9) = 323.7 W
Insert the following values:
T
40°C
int
T
30°C
ext
k
1.3
P
323.7 W
Then:
×
3
1.3
V
-------------------------------------- -
=
40 30
3
= 126.2 m
3.7
Enclosure design and drive ambient
temperature
Drive derating is required for operation in high ambient temperatures
Totally enclosing or through panel mounting the drive in either a sealed
cabinet (no airflow) or in a well ventilated cabinet makes a significant
difference on drive cooling.
The chosen method affects the ambient temperature value (T
should be used for any necessary derating to ensure sufficient cooling
for the whole of the drive.
The ambient temperature for the four different combinations is defined
below:
1. Totally enclosed with no air flow (<2 m/s) over the drive
T
= T
+ 5°C
rate
int
2. Totally enclosed with air flow (>2 m/s) over the drive
T
= T
rate
int
3. Through panel mounted with no airflow (<2 m/s) over the drive
T
= the greater of T
rate
4. Through panel mounted with air flow (>2 m/s) over the drive
T
= the greater of T
rate
Where:
T
= Temperature outside the cabinet
ext
T
= Temperature inside the cabinet
int
T
= Temperature used to select current rating from tables in
rate
Chapter 12 Technical Data on page 265.
Onboard
Advanced
Technical
PLC
parameters
Data
3
3
per hour (1 m
/hr = 0.59 ft
P
o
------ -
P
l
×
323.7
3
3
/hr (74.5 ft
/min) (1 m
/ hr = 0.59 ft
+5°C, or T
ext
int
or T
ext
int
UL Listing
Diagnostics
Information
3
/min)
3
/min)
) which
rate
49