Displaying the trip history

The drive retains a log of the last 10 trips that have occurred in Pr 10.20
to Pr 10.29 and the corresponding multi-module drive module number
(Pr 6.49 = 0) or the trip time (Pr 6.49 = 1) for each trip in Pr 10.41 to
Pr 10.51. The time of the trip is recorded from the powered-up clock (if
Pr 6.28 = 0) or from the run time clock (if Pr 6.28 = 1).
Pr 10.20 is the most recent trip, or the current trip if the drive is in a trip
condition (with the module number or trip time stored in Pr 10.41 and
Pr 10.42). Pr 10.29 is the oldest trip (with the module number or trip time
stored in Pr 10.51). Each time a new trip occurs, all the parameters
move down one, such that the current trip (and time) is stored in
Pr 10.20 (and Pr 10.41 to Pr 10.42) and the oldest trip (and time) is lost
out of the bottom of the log.
If any parameter between Pr 10.20 and Pr 10.29 inclusive is read by
serial communications, then the trip number in Table 13-1 Trip
indications on page 284 is the value transmitted.
13.5

Behaviour of the drive when tripped

If the drive trips, the output of the drive is disabled so that the drive stops
controlling the motor. If any trip occurs (except the UV trip) the following
read only parameters are frozen until the trip is cleared. This is to help in
diagnosing the cause of the trip.
Parameter
1.01
Frequency/speed reference
1.02
Pre-skip filter reference
1.03
Pre-ramp reference
2.01
Post-ramp reference
3.01
Frequency slaving demand/Final speed ref
3.02
Speed feedback
3.03
Speed error
3.04
Speed controller output
4.01
Current magnitude
4.02
Active current
4.17
Reactive current
5.01
Output frequency
5.02
Output voltage
5.03
Power
5.05
DC bus voltage
7.01
Analog input 1
7.02
Analog input 2
7.03
Analog input 3
Analog and digital I/O
The analog and digital I/O on the drive continue to work correctly if a trip
occurs, except the digital outputs will go low if one of the following trips
occur: O.Ld1, PS.24V.
Drive logic functions
The drive logic functions (i.e. PID, variable selectors, threshold
detectors, etc.) continue to operate when the drive is tripped.
Onboard PLC program
The Onboard PLC program continues to run if the drive is tripped, except
if one of Onboard PLC program trips occur.
Braking IGBT
The braking IGBT continues to operate even when the output of the
drive is not enabled (except if the low voltage DC supply is being used),
but is only disabled if any of the following trips occurs or would occur if
another trip had not already become active: OI.Br, PS, It.Br, OV or any
HFxx trip.
300
Electrical
Getting
Basic
installation
Started
parameters
Description
www.controltechniques.com
Running
SMARTCARD
Optimization
the motor
operation
Onboard
Advanced
Technical
Diagnostics
PLC
parameters
Data
Unidrive SP User Guide
Issue Number: 13
UL Listing
Information

Hide quick links:

Table of Contents
loading

Table of Contents