Mitsubishi Electric PFAV-P250VM-E Service Manual page 99

Hide thumbs Also See for PFAV-P250VM-E:
Table of Contents
[ VIII Control ]
(2) Dipswitches (Fresh Air Intake type)
1) SW1,3,7,8
Switch
Function
Room temperature detec-
1
tion position
2
Filter sign
3
4
5
Remote display option
SW1
6
7
Forced heating operation
8
Automatic recovery after
9
power failure
10
Power reset
1
Model setting
2
Capacity code
3
Forced Thermo-ON
Indoor unit fan operation
4
during defrost cycle
5
SW3
6
Heat dissipation
Automatic LEV value con-
7
version function
Negative 4°C [7.2°F] off-
8
set (heating)
9
10
1
Temp. value used to con-
2
trol indoor temp.
SW7
3
4
1
SW8
2
3
1) The setting timings for the dipswitches 1 and 3 is when the units are stopped (remote controller is switched off). Power reset
is not required.
2) The settings in the shaded areas indicate factory settings.
HWE10190
Function according to switch setting
OFF
Indoor unit return air
Filter sign
100h
SW1-2
OFF
SW1-3
OFF
-
-
Fan output
-
-
Disabled
-
-
Disabled
Disabled
Heat pump
Refer to the table on the setting combination with
Disabled
OFF
-
-
1 min. (heating only)
Not available
Enabled
-
-
-
-
-
-
Return air temp.
-
-
-
-
-
-
-
-
-
-
ON
Built-in sensor on the re-
mote controller
1 2 5 0 h
N / A
2 5 0 0 h
ON
OFF
ON
OFF
ON
ON
-
Thermo-ON signal
-
Enabled
-
Enabled
Enabled
Cooling-only
SW2.
Forced Thermo-ON
ON
-
3 min. 5 sec. (regardless
of the operation mode)
Available
Disabled
-
-
-
Supply air temp.
When indoor and
outdoor units are
-
-
-
-
-
- 90 -
Switch setting
timing
Notes
OFF
ON
P300,P600
Factory setting
SW1-2
SW1-3
When this switch is set to ON,
units are forced to operate in
the heating mode when the
return air dry temperature is at
or below 5°C[41°F].
Set these switches to OFF
when SWC is set to ON.
When the unit is
stopped (remote
controller is
switched off)
Return air temp. and preset
temp. are fixed.
Set this switch to ON (dis-
abled) on the floor-standing
models.
Factory settings for these
switches depend on the unit
capacity. Refer to section 2).
switched off
When the unit is
stopped (remote
controller is
switched off)
P900
ON
OFF
OFF
ON
GB