An Example Of A System To Which An Ma Remote Controller Is Connected - Mitsubishi Electric PFAV-P250VM-E Service Manual

Hide thumbs Also See for PFAV-P250VM-E:
Table of Contents
[ II Restrictions ]

[5] An Example of a System to which an MA Remote Controller is connected

1. Single-outdoor-unit system (manual IC/OC address setup)
(1) Sample control cable wiring configuration
(2) Cautions
1) Do not connect terminal blocks TB5 on the indoor units
that are connected to an outdoor unit in a different refrig-
erant circuit with each other.
2) No more than two MA remote controllers can be connect-
ed to a group of indoor units. To connect three or more
indoor units to the system, use two or less MA remote
controllers.
HWE10190
OC
51
TB3
TB7
M1 M2 S
M1 M2
OC
52
TB7
TB3
M1 M2 S
M1 M2
L1
Group
IC
01
TB5
M1 M2 S
MA (main body)
Group
IC
02
TB5
M1 M2 S 1 2
A B
A B
MA
MA (main body)
MA (sold separately)
Main
(3) Maximum allowable length
1) Indoor-outdoor transmission cable
Maximum cable distance (1.25 mm
L1≤200m [656ft]
2) Transmission cable for the centralized control system
No connection is required.
3) MA remote controller wiring
Total cable length (0.3 to 1.25mm
m1≤200m [656ft]
m2+m3≤200m [656ft]
- 26 -
TB15
1 2
A B
TB15
A B
Sub
2
[AWG16] min.)
2
[AWG22 to 16])