Mitsubishi Electric PFAV-P250VM-E Service Manual page 127

Hide thumbs Also See for PFAV-P250VM-E:
Table of Contents
[ IX Test Run Mode ]
(2) Heating operation
Specifications
Ambient
tempera-
ture
Operating
conditions
Piping
Refrigerant charge
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC(LEV1)
ing
LEV2
High pressure (after O/S)/Low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10190
Indoor unit
Outdoor unit
Indoor
Outdoor
Main pipe
Discharge (TH4)
Heat exchanger outlet
(TH3)
Accumulator inlet
Accumulator outlet
Compressor suction
Compressor shell bot-
tom
LEV inlet
Heat exchanger outlet
PFAV-P250VM-E
model
PUHY-P250YJM-A
model
20°C/- [68°F/-]
DB/WB
7°C/6°C [45°F/43°F]
m[ft]
7.5 [24-1/4]
kg
11.5 [25-6]
[lbs-oz]
A
12.5
V
400
Hz
71
406
Pulse
0
2100
MPa
2.85/0.61 [413/88]
[psi]
82 [180]
0 [32]
-2 [28]
-2 [28]
°C [°F]
-2 [28]
40 [104]
38 [100]
80 [176]
- 118 -
PFAV-P300VM-E-F
PUHY-P250YJM-A
7°C/- [45°F/-]
7°C/3°C [45°F/37°F]
7.5 [24-1/4]
11.5 [25-6]
13.5
400
71
708
0
2100
2.65/0.58 [384/84]
75 [167]
2 [36]
0 [32]
0 [32]
0 [32]
23 [73]
30 [86]
70 [158]
GB