Mitsubishi Electric PFAV-P250VM-E Service Manual page 27

Hide thumbs Also See for PFAV-P250VM-E:
Table of Contents
[ II Restrictions ]
1) M-NET transmission line
Facility
type
Type
Cable type
Number of
cores
Cable size
Maximum transmission
line distance between the
outdoor unit and the far-
thest indoor unit
Maximum transmission
line distance for central-
ized control and Indoor/
outdoor transmission line
(Maximum line distance
via outdoor unit)
HWE10190
Shielded cable CVVS, CPEVS, MVVS
500 m [1640ft] max.
*The maximum overall line length from the power supply unit on the transmission lines for
centralized control to each outdoor unit or to the system controller is 200m [656ft] max.
- 18 -
All facility types
2-core cable
2
Larger than 1.25mm
[AWG16]
200 m [656ft] max.