[ IX Test Run Mode ]
(2) Heating operation
Specifications
Ambient
tempera-
ture
Operating
conditions
Piping
Refrigerant charge
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
SC(LEV1)
ing
LEV2
High pressure (after O/S)/Low
Pressure
pressure (before accumulator)
Outdoor
unit
Temp. of
each sec-
tion
Indoor
unit
HWE10190
Indoor unit
Outdoor unit
Indoor
DB/WB
Outdoor
Main pipe
[lbs-oz]
Discharge (TH4)
Heat exchanger out-
let (TH3)
Accumulator inlet
Accumulator outlet
°C [°F]
Compressor suction
Compressor shell
bottom
LEV inlet
Heat exchanger out-
let
model
model
PUHY-P250YJM-A
m[ft]
kg
A
V
Hz
71
Pulse
2100
MPa
2.81/0.66 [408/96]
[psi]
82 [180]
0 [32]
-2 [28]
-2 [28]
-2 [28]
40 [104]
- 123 -
PFAV-P500VM-E
PUHY-P500YSJM-A
PUHY-P250YJM-A
20°C/- [68°F/-]
7°C/6°C [45°F/43°F]
7.5 [24-1/4]
22.5 [49-10]
27.1
400
71
406
0
2100
2.81/0.66 [408/96]
82 [180]
0 [32]
-2 [28]
-2 [28]
-2 [28]
40 [104]
37 [99]
80 [176]