Discharge Pipe Temperature Control - Daikin FTXS20G2V1B Service Manual

G-series
Hide thumbs Also See for FTXS20G2V1B:
Table of Contents
SiENBE04-808_A
3.4

Discharge Pipe Temperature Control

Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to
keep this temperature from going up further.
Detail
Function and Control
°C
°C
°C
Discharge pipe
temperature
Zone
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Drooping zone
The timer starts, and the frequency is drooping.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency is increased.
Reset zone
The upper limit of frequency is canceled.
20/25/35 class
(ºC)
110
(ºC)
105
(ºC)
101
(ºC)
99
(ºC)
97
42 class
50 class
110
110
103
103
102
101.5
100
100
95
95
Control Specification
Stop zone
°C
Drooping zone
Keep zone
Up zone
°C
Reset zone
(R4270)
Control
50