Outdoor Unit - RK(X)S20-35G2V1B9, ARXS20-35G3V1B
Step
3
Heat up the brazed part
of the suction side and
disconnect.
4
Lift the compressor up
and remove it.
237
Procedure
Suction side
SiENBE04-808_A
Points
Note:
„ Do not use a metal saw for
cutting pipes by all means
because the sawdust comes
into the circuit.
„ When withdrawing the pipes,
be careful not to pinch them
firmly with pliers. The pipes
may get deformed.
„ Provide a protective sheet or
a steel plate so that the
brazing flame cannot
(R12032)
influence peripheries.
„ Be careful so as not to burn
the compressor terminals,
the name plate, the heat
exchanger fin.
(R7254)