Mitsubishi Electric PURY-P72 Service Handbook page 180

Hide thumbs Also See for PURY-P72:
Table of Contents
[VIII Test Run Mode]
Outdoor unit model
Operation
PURY-P216TSHMU-A
PURY-P120THMU-A
PURY-P96THMU-A
Model name of BC controller
CMB-P1013NU-GA
Ambient
Indoor
26.7"C/19.4°C [80°F/67°F]
tempera-
DBIWB
ture
Outdoor
35°C/- [95°F/-]
No. of connected units
6
Unit
Indoor unit
No. of units in operation
6
Model
-
36/36/36/36/36/36
Operating
conditions
Main pipe
5 [16-3/8"]
Piping
Branch pipe
m
10
[32-314"]
[ft]
Total pipe length
65 [213-1/4'1
Fan speed
-
Hi
Amount of refrigerant
kg
43.0 [95]
Pbs-oz]
Electric current
A
53.8
Outdoor
Voltage
V
230
unit
Compressor frequency
Hz
75
65
LEV open-
Indoor unit
275/275/275/275/275/275
Pulse
ing
BC controller (1/2/3)
2000/2000/280
High pressure(63HS1)1
2.82/0.91
2.66/0.91
Low pressure(63LS)
MPa
[4091131]
[385/131]
Pressure
BC controller on the liquid side(PS1)/
[psi]
2.66/2.66
Intermediate part(PS3)
[3851385J
Discharge (TH4)
82 [180]
85 [185]
Heat exchanger outlet
43 [109]
39 [102]
(TH3)
Outdoor
Accumulator inlet
8 [46]
8 [46]
Temp. of
unit
each sec-
Accumulator outlet
°C
8 [46]
8 [46]
[oF]
tion
Compressor inlet
20 [68]
19
[66]
Compressor shell bottom
42 [108]
40 [104]
LEV inlet
22 (72J
Indoor unit
Heat exchanger inlet
9 [48]
HWE0803A
·170 -
GB