Mitsubishi Electric PURY-P72 Service Handbook page 196

Hide thumbs Also See for PURY-P72:
Table of Contents
[IX Troubleshooting]
1. Error Code
II
1302
I I
High pressure fault 1 (Outdoor unit)
2. Error definition and error detection method
1) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor during operation (the first detection), the out-
door stops once, tums to antirestart mode for 3 minutes, and restarts after 3 minutes automatically.
2) If the pressure of 3.78MPa [548psi] or higher is detected by the pressure sensor again (the second detection) within 30 min-
utes after the first stop of the outdoor unit, the outdoor unit stops once, turns to anti-restart mode for 3 minutes, and restarts
after 3 minutes automatically.
3) If the pressure of 3.87MPa [561 psi] or higher is detected by the pressure sensor (the third detection) within 30 minutes of the
second stop of the outdoor unit, the outdoor unit will make an error stop, and the error code -1302" will be displayed.
4) If the pressure of 3.78MPa [548psi] or higher is detected more than 30 minutes after the stop of the outdoor unit, the detection
is regarded as the first detection, and the operation described in step 1 above will start.
S) For 30 minutes after the stop of the outdoor unit, preliminary errors will be displayed on the LED display.
6) The outdoor unit makes an error stop immediately when not only the pressure sensor but also the pressure switch detects
4.1S+O,-0.15 MPa [601 +0,-22 psi]
7) Open phase due to unstable power supply voltage may cause the pressure switch to malfunction or cause the units to come
to an abnormal stop.
3. Cause, check method and remedy
Cause
Check method and remedy
(1 )
Indoor unit LEV actuation failure
Perform a heating operation and check the op-
BC controller LEV malfunction Heating only or heating main:
eration.
(2)
Cooling: LEV on the indoor unit
Indoor LEV 3
LEV1.2.3
Defrost : LEV3
SVM1.1 b.2.2b
(3)
BC controller SVM1 and 2 malfunction
SVA
->Cooling only or defrost
Heating: LEV on the indoor unit
(4)
BC controller SVA and SVC malfunction
LEV3
->Cooling only or cooling main
SVM2.2b
SVB.SV4a - 4d
(S)
BC controller SVB malfunction ->Heating only or heating main
Refer to the page on trOUbleshooting for LEV
Solenoid valve SV malfunction(4a-4c (P72 model) .4a-4d(P96
and solenoid valve.{page 279)
and P120 models» -:>Cooling only or cooling main
(6)
Port address settino error.
Confirm the port address of the indoor unit.
(7)
Refrigerant service valve actuation failure
Confirm that the refrigerant service valve is fully
(8)
Short cycle on the indoor unit side
Check the indoor units for problems and correct
(9)
Clogged filter on the indoor unit
them, if any.
(10)
Reduced air flow due to dirty fan on the indoor unit fan
(11 )
Dirty heat exchanger of the indoor unit
(12)
Indoor fan (including fan parts) failure or motor failure
Items (7) through (12) above reduce the condensing capability
of the unit, resulting in high-pressure rise during heating oper-
ation.
(13)
Short cycle on the outdoor unit
Check the outdoor units for problems and cor-
(14)
Dirty heat exchanger of the outdoor unit
rect them, if any.
(1S)
Outdoor fan (including fan parts) failure, motor failure, or fan
Check the fan on the outdoor unit.
controller malfunction
Refer to the section on troubleshooting the out-
Items (13) through (1S) above reduce the condensing capabil-
door unit fan.{page 279)
ity of the unit, resulting in high-pressure rise during cooling op-
eration.
(16)
Solenoid valve (SV1 a) malfunction
Refer to the section on troubleshooting the sole-
The by-pass valve (SV1 a) can not control rise in high pressure.
noid valve.(page 27S)
(17)
Thermistor failure (TH3, TH7)
Check the thermistor resistor.(page 217)
(18)
Pressure sensor failure
Refer to the page on the troubleshooting of the
high pressure sensor. (page 273)
(19)
Failure of the thermistor input circuit and pressure sensor input
Check the sensor temperature/pressure on the
circuit on the controller board
LED monitor.
(20)
Thermistor mounting problem (TH3, TH7)
Check the sensor temperature/pressure on the
(21)
Disconnected male connector on the pressure switch (63HS1)
LED monitor.
or disconnected wire
(22)
Voltage drop caused by unstable power supply voltage
Check the input voltage at the power supply ter-
minal block (TB1 \.
HWEOB03A
- 186-
GB