Mitsubishi Electric PURY-P-YGM-A Installation Manual

Air-conditioners for building application, outdoor unit, for use with r410a
Air-Conditioners For Building Application
OUTDOOR UNIT
PURY-P-YGM-A

INSTALLATION MANUAL

For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit.
INSTALLATIONSHANDBUCH
Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
MANUEL D'INSTALLATION
Veuillez lire le manuel d'installation en entier avant d'installer ce climatiseur pour éviter tout accident et vous assurer d'une utilisation correcte.
MANUAL DE INSTALACIÓN
Para un uso seguro y correcto, lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado.
MANUALE DI INSTALLAZIONE
Per un uso sicuro e corretto, leggere attentamente questo manuale di installazione prima di installare il condizionatore d'aria.
INSTALLATIEHANDLEIDING
Voor een veilig en juist gebruik moet u deze installatiehandleiding grondig doorlezen voordat u de airconditioner installeert.
MANUAL DE INSTALAÇÃO
Para segurança e utilização correctas, leia atentamente este manual de instalação antes de instalar a unidade de ar condicionado.
E°XEIPI¢IO O¢H°IøN E°KATA™TA™H™
РУКОВОДСТВО ПО УСТАНОВКЕ
MONTAJ ELK‹TABI
Emniyetli ve do¤ru biçimde nas›l kullan›laca¤›n› ö¤renmek için lütfen klima cihaz›n› monte etmeden önce bu elkitab›n› dikkatle okuyunuz.
For use with R410A
Table of Contents
loading

Summary of Contents for Mitsubishi Electric PURY-P-YGM-A

  • Page 1: Installation Manual

    Air-Conditioners For Building Application OUTDOOR UNIT PURY-P-YGM-A For use with R410A INSTALLATION MANUAL For safe and correct use, please read this installation manual thoroughly before installing the air-conditioner unit. INSTALLATIONSHANDBUCH Zum sicheren und ordnungsgemäßen Gebrauch der Klimageräte das Installationshandbuch gründlich durchlesen.
  • Page 2 [Fig. 5.0.1] = > : Top view = > : Side view : When there is little space up to an obstruction A : Front = > B : No restrictions on wall height (left and right) = >...
  • Page 3 (mm) [Fig. 8.2.1] Å Outdoor model ı High press. Side Ç Low press. Side (*Note1) P200 ø15.88 ø19.05 P250 ø19.05 ø22.2 A B C P300 ø19.05 ø22.2 P350 ø19.05 ø28.58 P400 ø22.2 ø28.58 P450 ø22.2 ø28.58 P500 ø22.2 ø28.58 P550 ø28.58 ø28.58 P600...
  • Page 4 [Fig. 9.3.1] [Fig. 9.3.2] A : Nitrogen gas A : System analyzer B : To indoor unit B : Lo knob C : System analyzer C : Hi knob D : Lo knob D : Ball valve E : Hi knob E : Low press.
  • Page 5 10.3 [Fig. 10.3.1] Change the jumper connector CN40 from CN41 to CN40 (51) (52) (01) (02) (55) (05) (06) SW2-1:ON M1 M2 S M1 M2 S M1 M2 M1 M2 S M1 M2 S M1 M2 S M1 M2 S M1 M2 S ...
  • Page 6: Table Of Contents

    Contents 1. Safety precautions ..................6 9. Additional refrigerant charge ..............10 1.1. Before installation and electric work .......... 6 9.1. Calculation of additional refrigerant charge ......10 1.2. Precautions for devices that use R410A refrigerant ....6 9.2. Precautions concerning piping connection and valve 1.3.
  • Page 7: Before Installation

    • Store the piping to be used during installation indoors and keep both • The reverse phase of L lines (L ) can detected (Error cord: 4103), ends of the piping sealed until just before brazing. (Store elbows and but the reverse phase of L lines and N line can not be detected. other joints in a plastic bag.) - Some electric parts may be damaged when power is supplied during miss - If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and...
  • Page 8: Specifications

    3. Specifications Model PURY-P200 PURY-P250 PURY-P300 PURY-P350 PURY-P400 Noise level (50/60 Hz) 56 dB 57 dB 59 dB 60 dB 61 dB External static pressure 0 Pa Indoor unit Total capacity 50 ~150 % Model 20 ~ 250 Quantity 1 ~ 15 1 ~ 16 1 ~ 16 1 ~ 20...
  • Page 9: Installation Of Unit

    7. Installation of unit 7.1. Installation Warning: • Be sure to install unit in a place strong enough to withstand its weight. [Fig. 7.1.1] (P.2) Any lack of strength may cause unit to fall down, resulting in a personal A M10 anchor bolt procured at the site. B Corner is not seated.
  • Page 10: Additional Refrigerant Charge

    9. Additional refrigerant charge At the time of shipping, the outdoor unit is charged with the refrigerant. As this 9.2. Precautions concerning piping connec- charge does not include the amount needed for extended piping, additional charg- tion and valve operation ing for each refrigerant line will be required on site.
  • Page 11: Airtight Test, Evacuation, And Refrigerant Charging

    G Service port Caution: [Use this port to evacuate the refrigerant piping and add an additional charge at • Always remove the connecting pipe from the ball valve and braze it out- the site. side the unit. Open and close the port using a double-ended wrench. - Brazing the connecting pipe while it is installed will heat the ball valve and Always reinstall the cap after operation is completed.
  • Page 12: Thermal Insulation Of Refrigerant Piping

    9.4. Thermal insulation of refrigerant piping Penetrations Be sure to give insulation work to refrigerant piping by covering liquid pipe and gas [Fig. 9.4.4] (P.4) pipe separately with enough thickness heat-resistant polyethylene, so that no gap Inner wall (concealed) ...
  • Page 13 2 Wiring examples • Controller name, symbol and allowable number of controllers. Name Symbol Allowable number of controllers Outdoor unit controller BC Controller (Master) One controller for one OC BC Controller (Slave) Zero, one or two controllers for one OC Transmission booster unit Zero or one unit for one OC (*1) Indoor Unit Controller...
  • Page 14: Wiring Of Main Power Supply And Equipment Capacity

    10.4. Wiring of main power supply and equipment capacity Schematic Drawing of Wiring (Example) [Fig. 10.4.1] (P.5) A Switch (breakers for wiring and current leakage) B Outdoor unit C BC controller (master) BC controller (slave) D Pull box E Indoor unit F Breakers for current leakage Thickness of wire for main power supply and On/Off capacities Minimum wire thickness (mm...
  • Page 15: Information On Rating Plate

    P600 P650 Refrigerant (R410A) 10.5 13.0 13.0 13.0 16.5 22.0 22.0 22.0 22.0 22.0 Allowable pressure (Ps) HP: 4.15 MPa, LP: 2.21 MPa Net weight MANUFACTURER: MITSUBISHI ELECTRIC CORPORATION AIR-CONDITIONING & REFRIGERATION SYSTEMS WORKS 5-66, TEBIRA, 6-CHOME, WAKAYAMA CITY, JAPAN...
  • Page 16 This product is designed and intended for use in the residential, commer- cial and light-industrial environment. • Low Voltage Directive 73/23/EEC The product at hand is • Electromagnetic Compatibility Directive 89/ based on the following EU regulations: 336/EEC • Pressure Equipment Directive 97/23/EC Please be sure to put the contact address/telephone number on this manual before handing it to the customer.

Table of Contents