Mitsubishi Electric PURY-RP200 Service Handbook page 55

Hide thumbs Also See for PURY-RP200:
Table of Contents
[ II Restrictions ]
(5) Address setting method
Pro-
ce-
Unit or controller
dure
s
1
Opera-
In-
tion with
door
the
unit
MA re-
mote
controller
MA
re-
mote
con-
troller
2
Opera-
In-
tion with
door
the
unit
ME re-
mote
controller
ME
re-
mote
con-
troller
3
LOSSNAY
Booster Unit, Water Hex
Unit
4
Outdoor unit
5
Auxiliary
BCcontroller (Sub)
outdoor
unit
BC controller
(Main)
HWE10020
Ad-
dress
set-
ting
range
Main
IC
01 to
Assign the smallest address to
unit
50
In a system with a sub BC con-
(i) Indoor unit to be connected to
(ii) Indoor unit to be connected to
(iii) Indoor unit to be connected to
Make the settings for the indoor
units in the way that the formula "(i)
< (ii) < (iii)" is true.
Sub
IC
01 to
Assign sequential numbers start-
ing with the address of the main
unit
50
unit in the same group +1. (Main
unit address +1, main unit address
+2, main unit address +3, etc.)
MA
Main re-
No
mote
set-
control-
tings re-
ler
quired.
MA
Settings to be made according
Sub
Sub
remote
remote
to the remote controller func-
control-
control-
tion selection
ler
ler
Main
IC
01 to
Assign the smallest address
unit
50
to the main unit in the group.
Sub
IC
01 to
Assign sequential numbers
starting with the address of the
unit
50
main unit in the same group
+1. (Main unit address +1,
main unit address +2, main
unit address +3, etc.)
RC
101 to
Main re-
Add 100 to the main unit ad-
mote
dress in the group.
150
control-
ler
Sub
RC
151 to
Add 150 to the main unit ad-
remote
200
dress in the group.
control-
ler
LC
01 to
Assign an arbitrary but unique
address to each of these units
BU,
50
after assigning an address to
AU
all indoor units.
OC
51 to
100
BS
51 to
Assign an address that equals the
sum of the smallest address of the
100
indoor units that are connected to
the sub BC controller and 50.
BC
OC+1
Setting method
the main unit in the group.
troller, make the settings for the
indoor units in the following or-
der.
the main BC controller
sub BC controller 1
sub BC controller 2
-
- 46 -
Notes
Assign an address smaller than that of
the indoor unit that is connected to the
ME remote controller.
Enter the same indoor unit group set-
tings on the system controller as the
ones that were entered on the MA re-
mote controller.
To perform a group operation of indoor
units that have different functions, des-
ignate the indoor unit in the group with
the greatest number of
Port number setting is required
Assign an address higher than those of
the indoor units that are connected to
the MA remote controller.
Make the initial settings for the indoor
unit group settings via the system con-
troller.
To perform a group operation of indoor
units that have different functions, des-
ignate the indoor unit in the group with
the greatest number of functions as the
main unit.
Port number setting is required.
Addresses that are assigned to the in-
door units that are connected to the sub
BC controller should be higher than the
addresses that are assigned to the in-
door units that are connected to the
main BC controller.
It is not necessary to set the 100s
digit.
To set the address to 200, set it to
00.
None of these addresses may over-
lap any of the indoor unit addresses.
To set the address to 100, set it to 50.
If the addresses that is assigned to the
main BC controller overlaps any of the
addresses that are assigned to the out-
door units or to the sub BC controller,
use a different, unused address within
the setting range.
The use of a sub BC controller requires
the connection of a main BC controller.
Facto-
ry set-
ting
00
Main
00
101
00
00
GB