Mitsubishi Electric PURY-RP200 Service Handbook page 60

Hide thumbs Also See for PURY-RP200:
Table of Contents
[ II Restrictions ]
(2) System that requires more than 16 BC controller ports or with multiple BC controllers
Outdoor unit
H
H'
Reducer (P15 - P50 models)
(Supplied with the BC Controller)
h1
Operation
Length
Total pipe length
Total pipe length from the out-
door unit to the farthest indoor
unit
Between outdoor unit and BC
controller
Between BC controller and in-
door unit
Height
differ-
Between indoor
ence
and outdoor
units
Between indoor unit and BC
controller
Between indoor units
Between the BC controller
(main or sub) and the sub BC
controller
*1. When the capacity of the connected indoor units is P200 or above, use the figures in the parentheses as a reference.
HWE10020
A
BC controller (main)
Junction pipe
a
b
(CMY-R160-J1)
Indoor
Indoor
(P15 - P80 models)
(P100 - P250 models)
Outdoor unit
above in-
door unit
Outdoor unit
below in-
door unit
Branch joint
C
Branch joint
B
d
c
Indoor
Indoor
Maximum of 3 units per port
Total capacity of P80 or below
Pipe sections
A+B+C+D+E+a+b+c+d+e+f
A+C+E+f
A
B+d or C+D+e
or C+E+f
H
H'
h1
h2
h3
- 51 -
Indoor
e
BC controller (sub)
D
BC controller (sub)
E
f
Indoor
Allowable length of pipes
220 [721] or less
100 [328] or less
(Equivalent length 125 [410] or less)
70 [229] or less
30 [98] or less
50 [164] or less
40 [131] or less
15 [49](10[32]) or less
15 [49](10[32]) or less
15 [49] or less
h1
h3
h2
h1
Unit: m [ft]
*1
*1
GB

Hide quick links: