Mitsubishi Electric PURY-RP200 Service Handbook page 157

Hide thumbs Also See for PURY-RP200:
Table of Contents
[ VIII Test Run Mode ]
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
HWE10020
Operation
Indoor
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
Discharge (TH4)
Heat exchanger inlet
(TH6)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
Outdoor unit model
PURY-RP300YJM-A
CMB-P104V-G1
20°C/-
[68°F/-]
DB/WB
7°C/6°C
[45°F/43°F]
3
Unit
3
-
112/112/112
5 [16-3/8"]
m
10 [32-3/4"]
[ft]
35 [114-13/16"]
-
Hi
kg
19.1 [43]
[lbs-oz]
A
15.3
V
400
Hz
81
332/332/332
Pulse
110/-/660
2.68/0.58
[389/84]
MPa
[psi]
2.64/2.32
[383/336]
81 [178]
0 [32]
-3 [27]
°C
-4 [25]
[°F]
-4 [25]
40 [104]
39 [102]
70 [158]
- 148 -