The 3364 Unit's Vo0 - Vo2; The 3377 Unit's Output (Siren); The 3379 Unit's Output (Sounder); The 4380 Unit's Output (Beacon) - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents
Panasonic Electric Works Nordic AB
MEW01351
Rev: -
12.6
12.7
12.8
12.9
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
The 3364 unit's VO0 – VO2
Each 3364 unit has two programmable, supervised (monitored)
voltage outputs:
Output VO0 Supervised (monitored) voltage output, 24V DC
Output VO1 Supervised (monitored) voltage output, 24V DC
Each 3364 unit also has one programmable special output, intended
for fire door closing (release magnets) only:
Output VO2 Voltage output, 24 V DC, max. 1A
For more information see the Technical Description MEW00529.
24 V DC is required from an external power supply unit (e.g. 3366).
Connections and more information, see dwg. 512 G3 – 31 & - 38.

The 3377 unit's Output (siren)

Each 3377 unit has one programmable output:
Output Siren
Three priority levels and three types of tones.
Connections and more information, see dwg. 512 G3 – 31.

The 3379 unit's Output (sounder)

Each 3378 unit has one programmable output:
Output Sounder
Three priority levels and three types of tones.
Connections and more information, see dwg. 512 G3 – 31.

The 4380 unit's Output (beacon)

Each 4380 unit has one programmable output:
Output Beacon
(Light output and flash rate are user selectable via
switches in the unit.)
Connections and more information, see dwg. 512 G3 – 31.
59
Cont. 1 A, during 10 ms 1.4 A.
71
55
59
59
59
. Normally high.