8
8.1
8.2
8.3
Planning Instructions Fire alarm system EBL512 G3, V1.1.x

TLON connection board 1590

On the EBL512 G3 control unit (5000 / 5001) main board (5010),
there are spaces and connectors for two TLON connection boards type
19
1590
.
In a single (standalone) control unit there shall be no TLON
connection board mounted.
A system, with two or more control units, uses a single TLON
Network or a redundant TLON Network (i.e. two TLON
Networks), see below.
The TLON connection boards are mounted on the main board (5010)
according to dwg. 512 G3 – 11 and the networks are connected to the
terminal block "J4" on main board according to dwg 512 G3 - 24.

Single TLON Network

In a single TLON Network (Network no. 0), the TLON connection
board (1590) shall be mounted in position no. 0 on the main board. A
single TLON Network is a violation to the EN54-13 standard.

Redundant TLON network

In a redundant TLON Network (Network no. 0 and no. 1), the TLON
connection boards (1590) shall be mounted in position no. 0 and
position no. 1 on the main board.
Normally only Network no. 0 will be in use and in case of a network
fault (i.e. open circuit or short circuit), Network no. 1 will be
automatically used until there is no fault on Network no. 0.
See also chapter "Control Unit / TLON Network", page 17.

Network programming

The PC program TLON Manager is used for the TLON Network
programming. TLON Manager V1.X will be replaced with the next
generation TLON Manager V2.0.
NOTE! By the TLON Network programming (installation), some
unique data will be stored in a TLON connection board (1590)
memory and some unique data will be stored in a main board (5010)
memory.
After replacing a TLON connection board to another (or replacing
both a TLON connection board and a main board), do "Replace",
"Update" and "Save" in TLON Manager.
After replacing a main board to another (not the TLON connection
board), do "Update" and "Save" in TLON Manager.
19
TLON connection board type 1590 will be replaced with the next
generation TLON connection board 5090 (now under development).