Short Circuit Isolators (Addressable) - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents
Panasonic Electric Works Nordic AB
MEW01351
Rev: -
9.1.4
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
connected to the COM loop but max. 10 per COM loop. Red
ABS plastic housing and PC lens. Low (0.5 Cd) or high (1 Cd)
light output is programmable. An output control expression is
programmed (via WinG3). For more technical data, see the
Product Leaflet.
The COM loop address is set with the Address setting tool
(3314).
The beacon has an address label on which the
programmed address can be written.
The Address setting tool (3314) is also used for mode setting:
NORMAL mode: Used for 4380 in system EBL512 G3.
2330 mode: Not used in system EBL512 G3.
2312 mode: Not used in system EBL512 G3.

Short circuit isolators (addressable)

Each COM loop short circuit isolator is to be programmed (via
WinG3) regarding:
COM loop address
Name (Normally not changed)
Sequence Number (Serial Number in the COM loop's A-
direction.)
Connections, see dwg 512 G3 - 31. (See especially the L / SA wire!)
4313 Analog base with isolator.
built-in short circuit isolator. In case of short circuit on the
COM loop, the number of disabled units will be minimised.
4313 is power supplied via the COM loop. For more
information, see the Product Leaflet. The COM loop address is
set with the Address setting tool (3314). The unit has an
address label on which the programmed COM loop address is to
be written.
The Address setting tool (3314) is also used for mode setting:
NORMAL mode: Used for 4313 in system EBL512 G3.
2330 mode: Not used in system EBL512 G3.
2312 mode: Not used in system EBL512 G3.
According to the EN54 standard, at least one short circuit isolator is
required per 32 alarm points on the COM loop. In the Australian and
New Zealand conventions at least one isolator per 40 alarm points.
Up to sixteen 4313 can be used, which gives seventeen loop segments.
Each isolator has to be given a Sequence Number, 00-15.
isolators have to be connected consecutively (Sequence Number 00-
01-02-03-04-05-06-07-08-09-10-11-12-13-14-15) in the COM loop's
A-direction. NOTE! EBL512 G3 has one built-in isolator in the-A
direction (no. "A") and one in the B-direction (no. "B").
39
This unit has replaced the Addr. isolator 4370.
39
4313 is an analog base with a
49
The