Alarm Acknowledgement Facility (Aaf) - Panasonic MEW01 351 Planning Manual

Fire alarm system
Table of Contents
Panasonic Electric Works Nordic AB
MEW01351
Rev: -
16.13
Planning Instructions Fire alarm system EBL512 G3, V1.1.x

Alarm Acknowledgement Facility (AAF)

This facility is used on the Australian market only.
The AAF function is similar to the "Alert Annunciation function" (see
page 102).
One AAF zone can consist of one to five analog smoke detectors
(4300 / 4301), one AAF buzzer (e.g. Sounder base 3379) and one
98
AAF Control (AAFC)
. All connected on one COM loop.
COM loop
Sounder Base 3379
AAF
PRESS TO ACKNOWLEDGE
FALSE ALARM
Figure 22. Alarm Acknowledgement Facility units.
AAF function (see also the flow chart in the following figure):
- One of the detectors in an AAF zone reaches its fire alarm level.
The AA Process starts and the AAF buzzer sounds.
- The Acknowledgement Period starts
(A Period=10-60 sec. -- programmable via WinG3).
- If it is a false alarm, acknowledge the alarm on the AAFC before
the A Period is ended.
- After acknowledgement an Investigation Period starts and the AAF
buzzer is silent
(I Period =0-3 min. -- programmable via WinG3).
The AA Process ends if all the detectors in the AAF zone becomes
normal again (goes below its fire alarm level) during the I Period.
If the A or I Periods run out during the AA Process and any detector
in the AAF zone still is over its fire alarm level, normal fire alarm(s)
will be activated.
98
This unit is available on the Australian market only.
104
Smoke detector (4300, 4301)
AAFC
LED
Non-latching switch