Time Events 1 To 5 - Honeywell DCP301 User Manual

Digital program controller
Table of Contents
Chapter 5. FUNCTIONS

Time events 1 to 5

Time events
The ON and OFF times or only the ON time can
be set for each event No. and segment. The fol-
lowing describes ON/OFF of output.
• When the ON time is smaller than the OFF
time, output is ON for the duration from the
ON time to the OFF time.
(See segments 1, 6 and 7 in the figure.)
• When only the ON time is set, output is ON
for the during from the ON time to the seg-
ment end point.
(See segments 2 and 5 in the figure.)
• When both the ON time and OFF time are not
set, output is OFF.
(See segment 3 in the figure.)
• Setting only the OFF time without an ON time
is not possible.
(See segment 3B in the figure.)
• Setting an ON time to be greater to or equal
than the OFF time is not possible.
(See segment 3C in the figure.)
• Only ON and OFF times set within the seg-
ment time are valid. Times straddling the next
segment are invalid. The ON and OFF times
set in the next segment are valid.
(See segments 4 and 5 in the figure.)
Accordingly, the ON and OFF times settings
at the segment end point are ignored.
However, ON and OFF times set for segment
end points when the END mode is shifted to
are valid.
(See segment 9 in the figure, and compare with
segment 10 in the END mode.)
• When the ON time is set to 0 (no OFF time
setting, or OFF time is greater than 0), output
becomes OFF at time 0.
If output at the previous segment end point was
ON at this time, the output status at the seg-
ment switching point does not momentarily
become OFF.
(See segments 5 and 6 in the figure.)
• The G.Soak standby time is not included in the
ON and OFF times.
(See segment 7 in the figure.)
5-6
Either of time events or segment No. events can be selected by the time event type item
in the event configuration data setup.
Segment
ON time
ON < OFF
OFF time
Output ON
Output OFF
Segment
2
ON time
Output turns OFF at
OFF time
end of segment even if
OFF time is not set.
Output ON
Output OFF
Segment
3B
ON time
No ON
OFF time
Output ON
Output OFF
Segment
4
Segment time
ON time
OFF time
ON-OFF time is invalid
Output ON
even if set in excess of
segment 4 time.
Output OFF
Segment
5
ON time
OFF time
Output ON
Output OFF
Segment
G.Soak standby
ON time
OFF time
Output ON
Segment time start
Output OFF
1
3
3C
ON = OFF ON > OFF
5
Advance to
segment 5
6
ON = 0
ON
continued
7

Hide quick links:

Table of Contents
loading

Table of Contents