Recalling factory trim - analog output
You can use the
as-shipped factory settings to the analog output trim.
This command can be useful for recovering from an inadvertent trim, incorrect plant
standard, or faulty meter.
Recall factory trim - analog output using a communication
device
Procedure
1. From the HOME screen, enter the fast key sequence:
2. Follow the steps within the communication device to complete the digital to analog
Recall factory trim - analog output using AMS Device Manager
Procedure
1. Right-click the device and go to Method → Calibrate → Restore Factory Calibration.
2. Select Next to set the control loop to manual.
3. Select Analog Output Trim under Select trim to recall and click Next.
4. Follow screen prompts to recall analog output trim.
Recall factory trim - analog output using a local operator
interface (LOI)
Procedure
See
Figure 5-7
Figure 5-7: Recall factory trim – analog output using LOI
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
5.8 
Switching HART
Some systems are not capable of communicating with HART
The following procedures list how to change HART revisions between HART Revision 7 and
HART Revision 5.
Emerson.com
Recall Factory Trim - Analog Output
3, 4, 3
Fast keys
trim using other scale.
for LOI instructions.
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO MENU
EXIT MENU
®
CALIBRAT
ZERO TRIM
LOWER TRIM
UPPER TRIM
ANALOG TRIM
FACTORY RECALL
BACK TO MENU
EXIT MENU
revision
Operation and maintenance
February 2024
command to restore the
FACTORY RECALL
SENSOR RECALL
ANALOG RECALL
BACK TO MENU
EXIT MENU
Revision 7 devices.
®
93