Basic Setup Of The Transmitter - Emerson Rosemount 2051 Reference Manual

Pressure transmitter with hart revision 5 and 7 selectable protocol
Hide thumbs Also See for Rosemount 2051:
Table of Contents
Reference Manual
00809-0100-4107
2.4.4 
Verifying process variables configuration
This section describes how to verify that the correct process variables are selected.
Verify process variables using a communication device
Procedure
On the HOME screen, enter the fast key sequence:
3, 2, 1
Verify process variables using AMS Device Manager
Complete the following steps to verify process variables with AMS Device Manager.
Procedure
1. Right-click the device and select Overview from the menu.
2. Select All Variables to display the primary, secondary, tertiary, and quaternary
2.5 

Basic setup of the transmitter

This section goes through the necessary steps for basic setup of a pressure transmitter.
Related information
Configuring scaled variable
2.5.1 
Setting pressure units
The Pressure Unit variable sets the unit of measure for the reported pressure.
Set pressure units using a communication device
Procedure
From the HOME screen, enter the fast key sequence:
2, 2, 1, 1, 4
Set pressure units using AMS Device Manager
Procedure
1. Right-click the device and select Configure.
2. Select Manual Setup and select desired units from the Pressure Units drop-down
3. Select Send when complete.
Emerson.com
variables.
menu.
Configuration
February 2024
17