Water Quality; Filling The Condensate Trap - Bosch Therm C 1210 ES Installation And Operating Instructions Manual

Indoor residential and commercial models
Hide thumbs Also See for Therm C 1210 ES:
Table of Contents
Installation instructions

4.10 Water quality

Water quality can have an impact on appliance longevity and
may void the manufacturer's warranty.
For water analysis data call your local water department, or if on
a well, have well water analyzed periodically. If water quality
exceeds one or more of the values specified below, Bosch
recommends consulting a local water treatment professional
for water softening/conditioning options.
Description
pH
TDS (total dissolved solids) mg/l or ppm
Total hardness
Aluminum
Chlorides
Copper
Iron
Manganese
Zinc
Table 29
Connecting the pressure relief valve (PRV)
A listed pressure relief valve must be installed at the time of
installation. No valve is to be placed between the PRV and the
heater. No reducing coupling or other restriction may be
installed in the discharge line. The discharge line must be a
minimum of 4" above a drain and installed such that it allows
complete drainage of both the PRV and the line. The discharge
line must be placed where it will not cause any damage.
The location of the PRV must be readily accessible for servicing
or replacement, and be mounted as close to the water heater as
possible. See fig. 33. To install the PRV, a suitable fitting
connected to an extension on a "T" fitting can be sweated to the
hot water line.
Support all piping.
40
Max. Levels
pH
6.5 - 8.5
500
mg/l or ppm
100 (6 grains)
mg/l or ppm
2.0
mg/l or ppm
250
mg/l or ppm
1.0
mg/l or ppm
0.3
mg/l or ppm
0.05
mg/l or ppm
5.0
Fig. 33
Plumbing Connections (with shutoff valves) and
Pressure Relief Valve
[1] Pressure relief valve

4.11 Filling the condensate trap

The condensate trap can be filled before or after connecting the
vent pipe.
Filling the condensate trap before vent pipe installation
WARNING:
▶ Prior to initial start up, and after appliance has been out of
use for a long time or after cleaning the siphon, make sure
that you fill the condensate trap with water. This is to
prevent dangerous exhaust gases from entering the
building.
▶ Fill the condensate trap by pouring approx.14 oz. (400ml)
of water into the exhaust accessory on the top of the
appliance, see fig. 34.
C 1210ES/ESC – 6 720 644 887 (2022/04)