4.3.3 Vent configuration examples
Below are approved examples of vertical and horizontal venting
installations.
Fig. 11
Vertical venting system (single pipe penetration)
[1] Drain tee
[2] Intake
[3] Exhaust
[LA] Maintain 12 in. (18 in. for Canada) minimum clearance
above highest anticipated snow level maximum of 24 in.
above roof.
24
Fig. 12
Horizontal venting installation (combustion air
piping not shown)
[1] Termination
[2] Minimum above ground or normally expected snow
accumulation level
[3] Appliance
[4] Elbow (note: minimum 1ft of straight vent pipe required)
[5] Horizontal run ¼" per foot down to termination
WARNING:
▶ Single pipe penetration should be used in non-freezing
climates only and steps must be taken to ensure that
adequate combustion air is available to the water heater at
all times!