To input Callendar-Van Dusen constants, perform the following procedure:
1.
2.
3.
4.
5.
6.
Note
When the transmitter-sensor matching is disabled, the transmitter reverts to factory trim.
Make certain the transmitter engineering units default correctly before placing the
transmitter into service.
2.9

Advanced setup

2.9.1

LCD display

The LCD display configuration command allows customization of the LCD display to suit
application requirements. The LCD display will alternate between the selected items:
Reference
20
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
From the HOME screen, select 2 Configure, 1 Guided Setup, 1 Configure Sensor,
1 Configure Type and Units and press Enter.
Select Cal VanDusen at the Select Sensor Type prompt.
Select the appropriate number of wires at the Select Sensor Connection prompt.
Enter the R
, Alpha, Delta, and Beta values from the stainless steel tag attached to
o
the special-order sensor when prompted.
Select desired other options and select Enter.
To disable the Transmitter-sensor matching feature from the HOME screen select
Configure>Guided Setup>Configure Sensor>Configure Sensor Type and Units and press
Enter. Select the appropriate sensor type from the Select Sensor type prompt.
Temperature units
Sensor temperature
% of range
Supply voltage
"LCD display screen messages" on page 43
Reference Manual
00809-0200-4648, Rev BB
for images of LCD display screens.
Configuration