This manual provides information on planning, mounting, wiring, and initial setup of the Micro Motion transmitter. For information on full configuration, maintenance, troubleshooting, or service of the transmitter, see the Micro Motion 5700 with Ethernet Transmitters: Configuration and Use Manual.
The information in this document assumes that users understand basic transmitter and sensor installation, configuration, and maintenance concepts and procedures.
This document uses the following criteria for hazard messages based on ANSI standards Z535.6-2011 (R2017).
Serious injury or death will occur if a hazardous situation is not avoided.
Serious injury or death could occur if a hazardous situation is not avoided.
Minor or moderate injury will or could occur if a hazardous situation is not avoided.
NOTICE
Data loss, property damage, hardware damage, or software damage can occur if a situation is not avoided. There is no credible risk of physical injury.
Physical access
Unauthorized personnel can potentially cause significant damage and/or misconfiguration of end users' equipment. Protect against all intentional or unintentional unauthorized use.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access to protect users' assets. This is true for all systems used within the facility.
You can find all product documentation on the product documentation DVD shipped with the product or at Emerson.com.
See any of the following documents for more information:
Preferred orientation | Alternate orientations | |
Variable | Setting |
Tag | |
Mass flow units | |
Volume flow units | |
Density units | |
Temperature units | |
Channel configuration | |
mA Output 1 | |
mA Output 2 (optional) |
|
Variable | Setting |
Frequency output (optional) |
|
Discrete output (optional) |
|
Discrete input (optional) |
|
Calibration parameters (for 9-wire installations only) | |
Flow calibration factor | FCF (Flow cal or flow calibration factor): |
Density calibration factors |
|
Self-switching AC/DC input, automatically recognizes supply voltage:
Note
For DC power:
Cable sizing formula
M = 18V + (R x L x 0.7A)
Typical power cable resistance at 68°F (20.0°C)
Wire gauge | Resistance |
14 AWG | 0.0050 Ω/ft |
16 AWG | 0.0080 Ω/ft |
18 AWG | 0.0128 Ω/ft |
20 AWG | 0.0204 Ω/ft |
2.5 mm2 | 0.0136 Ω/m |
1.5 mm2 | 0.0228 Ω/m |
1.0 mm2 | 0.0340 Ω/m |
0.75 mm2 | 0.0460 Ω/m |
0.50 mm2 | 0.0680 Ω/m |
The maximum cable length between the sensor and transmitter, which are installed separately, is determined by cable type.
Cable type | Wire gauge | Maximum length |
Micro Motion 4-wire remote mount | Not applicable |
|
Micro Motion 9-wire remote mount | Not applicable | 1,000 ft (305 m)(1) |
User-supplied 4-wire | VDC 22 AWG (0.326 mm²) | 300 ft (91 m) |
VDC 20 AWG (0.518 mm²) | 500 ft (152 m) | |
VDC 18 AWG (0.823 mm²) | 1,000 ft (305 m) | |
RS-485 22 AWG (0.326 mm²) or larger | 1,000 ft (305 m) |
(1) For Smart Meter Verification, the limit is 60 ft (18 m).
You can install the 5700 Ethernet transmitter in star, ring, or daisy-chain networks using industrial-rated shielded Ethernet cables.
5700 Ethernet transmitters can be installed in a star network
Figure 1: 5700 star network
Note
The External Ethernet switch must be a managed switch capable of Spanning Tree Protocol (STP) or similar functions.
5700 Ethernet transmitters can be installed in a ring network.
Figure 2: 5700 ring network
Note
The PLC must be a managed switch capable of Spannng Tree Protocol (STP) or similar functions.
5700 Ethernet transmitters can be installed in a daisy-chain network.
Figure 3: 5700 daisy-chain network
There are no separate mounting requirements for integral transmitters, and there is no need to connect wiring between the transmitter and the sensor.
There are two options available for mounting 5700 transmitters:
Prerequisites
Procedure
Figure 6: Wall-mounting bracket and dimensions for an aluminum transmitter
Figure 7: Wall-mounting bracket and dimensions for a stainless steel transmitter
Figure 8: Attaching and securing an aluminum transmitter to the mounting bracket
Tip
To ensure the mounting bracket holes are aligned, insert all attachment bolts into place before tightening.
Prerequisites
Procedure
For pole-mount installations, fit the U-bolt mounting piece to the instrument pole.
Figure 9: Pole-mounting bracket attachment for an aluminum transmitter
Figure 10: Pole-mounting bracket attachment for a stainless steel transmitter
Use this procedure to wire a 4-wire or 9-wire remote-mount transmitter to the sensor.
Prerequisites
Procedure
Terminate the 4-wire cable drain wires only at the sensor/core processor end of the cable. See the sensor installation manual for more detail. Do not connect the 4-wire cable drain wires to the ground screw located inside the junction box.
Figure 13: 4-wire transmitter-to-sensor wiring connections
Figure 14: 9-wire transmitter-to-sensor wiring connections
Note
Connect the four drain wires in the 9-wire cable to the ground screw located inside the junction box.
In 4-wire or 9-wire remote installations, the transmitter and sensor are grounded separately.
Prerequisites
NOTICE
Improper grounding could cause inaccurate measurements or meter failure.
Improper grounding could result in an explosion causing death or serious injury.
Note
For hazardous area installations in Europe, refer to standard EN 60079-14 or national standards.
If national standards are not in effect, adhere to the following guidelines for grounding:
Procedure
Figure 15: Internal ground screw
Figure 16: External ground screw
In integral installations, you can rotate the transmitter on the sensor up to 360° in 45° increments.
Procedure
Over rotating the housing can lead to damaging the feedthrough cable.
Figure 18: Rotate transmitter head
Figure 19: Re-attachment of the sensor clamp
The user interface on the transmitter electronics module can be rotated 90°, 180°, or 270° from the original position.
Figure 20: Display components
Procedure
In remote-mount installations, you can rotate the sensor wiring junction box on the transmitter plus or minus 180º.
Procedure
Signal | Channel A | Channel B | Channel C |
Channel options | EtherNet/IP™ The same protocol must be ordered on both Channel A and B. ProLink™ III and the Integrated Web server can always be connected to either Channel A or B. | EtherNet/IP | mA output |
Modbus™ TCP | Modbus TCP | Frequency output | |
PROFINET® | PROFINET | Discrete output | |
N/A | N/A | Discrete input |
The Channel 5700 I/O can be configured as:
Procedure
Remove the wiring access cover to reveal the I/O wiring terminal block connectors.
Figure 24:
Wire the mA Output for explosion-proof, nonincendive, or nonhazardous installations.
Prerequisites
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Figure 25: Internally-powered mA Output wiring
Figure 26: Externally-powered mA Output wiring
A
Figure 27: Externally-powered mA Output: maximum loop resistance
Wire the Frequency Output in explosion-proof, nonincendive, or nonhazardous installations.
Prerequisites
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Figure 28: Internally-powered FO wiring
Figure 29: Internally-powered FO: output amplitude versus load resistance [24 VDC (Nom) open circuit]
Figure 30: Externally-powered FO wiring
Wire the Discrete Output in explosion-proof, nonincendive, or nonhazardous installations.
Prerequisites
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate output terminal and pins.
Figure 31: Internally-powered DO wiring
Figure 32: Internally-powered DO: output amplitude versus load resistance [24 VDC (Nom) open circuit]
Figure 33: Externally-powered DO wiring
Prerequisites
Wire the Discrete Input in explosion-proof, nonincendive, or nonhazardous installations.
Meter installation and wiring should be performed only by suitably-trained personnel using the appropriate government and corporate safety standards.
Procedure
Wire to the appropriate input terminal and pins.
Figure 34: Internally-powered DI wiring
Figure 35: Externally-powered DI wiring
Note
Use this procedure if you are using an M12-terminated cable to wire the I/O channel.
Prerequisites
Obtain an A-coded M12-terminated cable.
Procedure
Pin identification | Wire color | Outputs |
Pin 1 | Not used | Not used |
Pin 2 | White | Positive terminal |
Pin 3 | Not used | Not used |
Pin 4 | Black | Neutral terminal |
To meet the EC Directive for Electromagnetic Compatibility (EMC), use a suitable shielded Cat5e, or higher-rated instrumentation cable to connect the meter. The instrumentation cable should have an overall screen to cover all cores. Where permissible, connect the overall screen to earth at the host end (360° bonded).
Prerequisites
When using a pre-terminated RJ45 cable, ensure there is no protective boot on the connector, as a protective boot will not fit through the conduit. Alternatively, you can use the RJ45 connector using a shielded-field termination connector.
Procedure
Example
Procedure
Example
Prerequisites
Obtain two D-coded M12-terminated Ethernet cables.
Procedure
Figure 37: M12 cables to the Ethernet I/O
Note
Depending on what type of M12 Ethernet option you have, your transmitter may have only the two Ethernet I/O connectors.
Table 2: M12 Ethernet I/O pinouts
Pin identification | Wire color | Outputs on RJ45 | Signal name |
Pin 1 | Orange/White | Pin 1 | TDP1/RDP2 |
Pin 2 | Green/White | Pin 3 | RDP1/TDP2 |
Pin 3 | Orange | Pin 2 | TDN1/RDN2 |
Pin 4 | Green | Pin 6 | RDN1/RDN2 |
You can install a user-supplied switch in the power supply line.
For compliance with the Low Voltage Directive 2014/35/EU (European installations), verify that the transmitter is located in close proximity to a switch.
Procedure
Figure 38: Location of power supply wiring terminals and equipment ground
NOTICE
Do not use the conduit specified for power supply wires for input/output wiring (see Figure 38) to avoid pinched wires when the cover is closed.
Use this procedure if you are using an M12-terminated cable to wire the power supply.
Prerequisites
Obtain an S-coded M12-terminated cable.
Procedure
Figure 39: M12-terminated cable to power supply
Note
For M12 power supply pinouts, only pins 1 and 3 are used.
Table 3: M12 power supply pinouts
Pin identification | Wire color | Outputs on board | Signal name |
Pin 1 | Brown | Terminal 3 | VDC + |
Pin 2 | White | Terminal 1 | Channel B + |
Pin 3 | Blue | Terminal 4 | VDC - |
Pin 4 | Black | Terminal 2 | Channel B - |
Use this section to set up printing with a 5700 Ethernet transmitter and an Epson TM-T88VI Ethernet printer. For information on configuring the printer, see Micro Motion 5700 with Ethernet Transmitters: Configuration and Use Manual.
There are two ways to set up printing:
Use this procedure to set up printing with a 5700 Ethernet transmitter and an Epson TM-T88VI printer by changing the printer's default IP address.
Procedure
Display | Menu → Configuration → Ethernet Settings → Network Settings |
ProLink III | Device Tools → Configuration → Network Settings |
For instructions on how to configure the transmitter and PC Ethernet settings, see the Micro Motion 5700 with Ethernet Transmitters: Configuration and Use Manual.
Display | Menu → Configuration → Printer → Printer IP address |
ProLink III | Device Tools → Configuration → Printer and Tickets |
Web browser | Configuration → Printer and Tickets |
Display | Menu → Operations → Printer → Print Ticket → Print Test Page |
ProLink III | Device Tools → Configuration → Printer and Tickets |
Web browser | Configuration → Printer and Tickets |
For instructions on how to configure print ticket options, see the Micro Motion 5700 with Ethernet Transmitters: Configuration and Use Manual.
If needed, see Function Check Failed in the Status alerts, causes, and recommendations section of the Micro Motion 5700 with Ethernet Transmitters: Configuration and Use Manual.
Use this procedure to set up printing with a 5700 Ethernet transmitter and an Epson TM-T88VI printer using the printer's default IP address.
Procedure
It can take 1-2 minutes for the printer to finish configuring network settings. When complete, the following ticket prints.
IP Address: 192.168.192.168
SubnetMask: 255.255.255.0
Gateway: 0.0.0.0 DHCP: No server - > Static
From the display | From ProLink III |
|
|
From the display | From ProLink III |
Go to Menu → Configuration → Ethernet Settings → Network Settings → IP address. | Go to Device Tools → Configuration → Network Settings. |
From the display | From ProLink III |
Go to Menu → Configuration → Ethernet Settings → Network Settings → Subnet Mask. | Go to Device Tools → Configuration → Network Settings. |
From the display | From ProLink III |
Go to Menu → Configuration → Printer → Printer Type. | Go to Device Tools → Configuration → Printer and Tickets. |
Use this procedure if you forgot the IP address of your printer and need to reset the default (192.168.192.168).
Procedure
Do not turn off power until the process is complete.
When complete, a Resetting to Factory Default Finished message displays.
A functional check alert is commonly triggered due to the following conditions:
The functional check alert is cleared after a successful print.
The transmitter must be powered up for all configuration and commissioning tasks, or for process measurement.
Procedure
Postrequisites
Although the sensor is ready to receive process fluid shortly after power-up, the electronics can take up to ten minutes to reach thermal equilibrium. Therefore, if this is the initial startup, or if power has been off long enough to allow components to reach ambient temperature, allow the electronics to warm up for approximately ten minutes before relying on process measurements. During this warm-up period, you may observe minor measurement instability or inaccuracy.
At initial startup of the transmitter, the guided configuration screen appears on the transmitter display. This tool guides you through basic configuration of the transmitter. The guided setup allows you to upload configuration files, set the transmitter display options, configure channels, and review sensor calibration data.
The transmitter display interface includes a display (LCD panel) and four optical switches – left, up, down, and right arrow keys – used to access the display menus and navigate the display screens.
Procedure
The transmitter only detects one switch selection at a time. Be sure to place your thumb or finger directly over a single optical switch, and ensure no other switches are being obstructed.
Figure 40: Proper finger positioning for activating an optical switch
When using the arrow keys, you must first activate the optical switch then release the same switch by removing your finger from the glass to move up, down, right, left or to make a selection. To enable auto-scroll when navigating up or down, activate the appropriate switch and continue to hold for one second. Release the switch when the desired selection is highlighted.
Figure 41: Example 1: Active arrow indicators on the transmitter display
Figure 42: Example 2: Active arrow indicators on the transmitter display
Use the service port connection to download or upload data from/to the transmitter. To access the service port, you can use commonly-available USB hardware, such as a USB drive, or USB cable.
If the transmitter is in a hazardous area, do not remove the housing cover while the transmitter is powered up. Failure to follow these instructions can cause an explosion resulting in injury or death.
The service port connection is located under the transmitter cap.
Use this procedure to wire the Discrete Output on the 5700 Ethernet transmitter to the 3100 transmitter relays for single-stage batch control.
Prerequisites
Procedure
Figure 43: Wiring for 5700 Ethernet Channel DO to 3100 relays
For more information: Emerson.com/global
Safety messages are provided throughout this manual to protect personnel and equipment. Read each safety message carefully before proceeding to the next step.
Safety and approval information
This Micro Motion product complies with all applicable European directives when properly installed in accordance with the instructions in this manual. Refer to the EU Declaration of Conformity for directives that apply to this product. The following are available: the EU Declaration of Conformity, with all applicable European directives, and the complete ATEX installation drawings and instructions. In addition, the IECEx installation instructions for installations outside of the European Union and the CSA installation instructions for installations in North America are available at Emerson.com or through your local Micro Motion support center.
Information affixed to equipment that complies with the Pressure Equipment Directive, can be found at Emerson.com. For hazardous installations in Europe, refer to standard EN 60079-14 if national standards do not apply.
Other information
Troubleshooting information can be found in the appropriate Configuration and Use Manual.
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Thank you! Your question has been received!
Need Assistance?
Do you have a question about the Micro Motion 5700 that isn't answered in the manual? Leave your question here.