Overview Of Electrical Connections; Router - Daikin EGSAH10UDA9W Installation Manual

Hide thumbs Also See for EGSAH10UDA9W:
Table of Contents
System requirements
The requirements posed on the heat pump system depend on the
LAN adapter application/system layout.
App control
Item
LAN adapter software It is recommended to ALWAYS keep the
LAN adapter software up-to-date.
Unit control method
On the user interface, make sure to set
[2.9]=2 (Control = Room thermostat)
Smart Grid application
Item
LAN adapter software It is recommended to ALWAYS keep the
LAN adapter software up-to-date.
Unit control method
On the user interface, make sure to set
[2.9]=2 (Control = Room thermostat)
Domestic hot water
To allow for energy buffering in the domestic
settings
hot water tank, on the user interface, make
sure to set [9.2.1]=4 (Domestic hot water
= Integrated).
Power consumption
On the user interface, make sure to set:
control settings
▪ [9.9.1]=1 (Power consumption control
= Continuous)
▪ [9.9.2]=1 (Type = kW)
INFORMATION
For instructions on how to perform a software update, see
the installer reference guide.
5.15.2

Overview of electrical connections

Connectors
1
2
a1
3
X1A
4
N
a2
L
b
1
X2A
2
c
X3A
d
X4A
a1
To solar inverter/energy management system
a2
230 V AC detection voltage
b
To electricity meter
c
Factory-mounted cable to indoor unit (P1/P2)
d
To router (via the factory-mounted Ethernet cable outside
of the unit)
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598591-1A – 2019.12
Requirement
Requirement
Connections
Field-supplied cables:
Connection
Cable section
Router (via the
factory-mounted
Ethernet cable
outside of the
unit, which is
coming from
X4A)
Electricity meter
0.75~1.25 mm
(X2A)
Solar inverter/
0.75~1.5 mm
energy
management
system +
230 V AC
detection
voltage (X1A)
(a)
Ethernet cable: Respect the maximum allowed distance
between LAN adapter and router, which is 50 m in case of
Cat5e cables, and 100 m in case of Cat6 cables.
(b)
These wires MUST be sheathed. Recommended strip
length: 6 mm.
(c)
All wiring to X1A MUST be H05VV. Required strip length:
7 mm. For more information, see
energy management
5.15.3

Router

Make sure the LAN adapter can be connected via a LAN connection.
The minimum category for the Ethernet cable is Cat5e.
To connect the router
Use one of the following ways (A, B or C) to connect the router:
a
a
Factory-mounted Ethernet cable
b
Router (field supply)
c
Smartphone with app control (field supply)
#
Router connection
A
Wired
a
d Field-supplied Ethernet cable:
▪ Minimum category: Cat5e
▪ Maximum length:
▪ 50 m in case of Cat5e cables
▪ 100 m in case of Cat6 cables
5 Electrical installation
Wires
Maximum
cable length
50/100 m
2
(b)
2
100 m
2
Depends on
100 m
(c)
application
"5.15.5 Solar inverter/
system" [ 4  27].
A/B/C
c
d
b
Installation manual
(a)
c
b
25