2 Connect the valve control cable to the appropriate terminals as
shown in the illustration below.
NOTICE
Wiring is different for a NC (normally closed) valve and a
NO (normally open) valve.
M2S
NO
X2M
3 Fix the cable with cable ties to the cable tie mountings.
5.6

To connect the electricity meters

Wires: 2 (per meter)×0.75 mm²
Electricity meters: 12 V DC pulse detection (voltage supplied
by PCB)
[9.A] Energy metering
INFORMATION
In case of an electricity meter with transistor output, check
the polarity. The positive polarity MUST be connected to
X5M/6 and X5M/4; the negative polarity to X5M/5 and
X5M/3.
1 Open the following (see
"3.2.1 To open the indoor
1 Top panel
2 User interface panel
3 Installer switch box cover
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598591-1A – 2019.12
NC
OR
X2M
unit" [ 4  7]):
1
2 Connect the electricity meters cable to the appropriate terminals
as shown in the illustration below.
3 Fix the cable with cable ties to the cable tie mountings.
5.7
To connect the domestic hot water
pump
Wires: (2+GND)×0.75 mm²
DHW pump output. Maximum load: 2 A (inrush), 230 V AC,
1 A (continuous)
[9.2.2] DHW pump
[9.2.3] DHW pump schedule
1 Open the following (see
1 Top panel
2 User interface panel
3 Installer switch box cover
3
2
5 Electrical installation
S3S
S2S
X5M
unit" [ 4  7]):
"3.2.1 To open the indoor
Installation manual
1
3
2
19