Page 1
AIR CONDITIONER Wall mounted type DESIGN & TECHNICAL MANUAL INDOOR ASTG09KMTC ASTG12KMTC OUTDOOR AOTG09KMTC AOTG12KMTC DR_AS079EF_01 2019.04.23...
Page 2
• Product specifications and design are subject to change without notice for future improvement. • For further details, please check with our authorized dealer. Trademarks ™ FGLair is trademark of Fujitsu General Limited in the United States, other countries or both. ™ Google Play is trademark of Google Inc. ®...
1. Specifications Wall mounted Type Inverter heat pump Model name ASTG09KMTC ASTG12KMTC Power supply 240 V ~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Star rating index 10-star standard Rated Btu/h 8,500 11,900 Cooling 0.9—3.6 0.9—4.1...
2. Dimensions 2-1. Models: ASTG09KMTC and ASTG12KMTC Unit: mm (834) Outline of indoor unit for pipe inlet Ø65 for pipe inlet Ø65 - 3 - 2-1. Models: ASTG09KMTC and ASTG12KMTC 2. Dimensions...
2-2. Installation space requirement Provide sufficient installation space for product safety. Unit: mm 70 or more 40 or more Wall hook bracket 107 or more Outline of the indoor unit 183 or more 1,500 or more - 4 - 2-2. Installation space requirement 2.
Airflow Rate (AFR): For cooling capacity: Total Capacity (TC), Sensible Heat Capacity (SHC), and Input Power (IP) For heating capacity: Total Capacity (TC) and Input Power (IP) 4-1. Cooling capacity ¢ Model: ASTG09KMTC Indoor temperature °CDB °CWB °CDB...
5. Fan performance 5-1. Air velocity distributions ¢ Models: ASTG09KMTC and ASTG12KMTC Fan speed Operation mode Measuring conditions HIGH Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Center Unit: m/s Top view Vertical airflow direction louver: Up Horizontal airflow direction louver: Left &...
6-2. Sound level check point Microphone Microphone NOTE: Detailed shape of the actual indoor unit might be slightly different from the one illustrated above. - 12 - 6-2. Sound level check point 6. Operation noise (sound pressure)
7. Safety devices Model Type of protection Protection form ASTG09KMTC and ASTG12KMTC Circuit protection Current fuse (PCB*) 250 V, 3.15 A 125±10°C Activate Fan motor stop Power IC thermal Fan motor protection shutdown protection 100±10°C Reset Fan motor restart *PCB: Printed Circuit Board - 13 - 7.
8-1. External input With using external input function, some functions on this product can be controlled from an external device. • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable should be used. Maximum length of cable is 150 m. •...
8-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ External input and output PCB • A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m. •...
8-3. Combination of external input and output By combining the function setting of the indoor unit and rotary switch setting of the External input and output PCB, you can select various combinations of functions. Combination examples of external input and output are as follows: External input External input Mode...
8-4. Details of function ¢ Control input function • When function setting is “Operation/Stop” mode 1 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting input and output PCB Off → On Operation External input and 46-00...
Page 23
• When function setting is “Forced stop” mode – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting input and output PCB Off → On Forced stop External input and 46-02 CN313 output PCB On →...
Page 24
• When function setting is “Operation/Stop” mode 2 – In the case of “Edge” input: Function Rotary SW on External External input Input signal Command setting input and output PCB Off → On Operation External input and 46-03 CN313 Stop (R.C. output PCB On →...
Page 25
• Forced thermostat off function Rotary SW on External External input Input signal Command input and output PCB Off → On Thermostat off External input and output PCB CN313 On → Off Normal operation Input Compressor Room temp. Set temp. - 21 - 8-4.
Page 26
¢ Control output function • Operation/Stop status Rotary SW on External Output External output Command input and output PCB signal Off → On Operation External input and output PCB CN310 On → Off Stop The output is low when the unit is stopped. Operation Indoor unit Stop...
Page 27
• Design and install external heater appropriately with considering its protection. • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - 23 - 8-4.
Page 28
Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
Page 29
Heat pump prohibition control Perform heating by external heater only. Indoor unit is continuous thermostat off. Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
Page 30
Auxiliary heater control by outdoor temperature 1 This control selects heat pump or external heater according to the outdoor temperature. When out- door temperature is high, the heating is performed by using heat pump only. Operation Condition Heater on Heater is on as shown in following diagram of heating temperature.
Page 31
• Operation status 8°C 6°C Outdoor temperature (Factory setting) -18°C -20°C Heat pump Heat pump Combination zone prohibition only zone Outdoor temperature zone * zone Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
Page 32
Auxiliary heater control by outdoor temperature 2 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Condition Heater on...
Page 33
• Operation status 8°C 6°C Outdoor temperature (Factory setting) -18°C -20°C Heat pump Combination zone Outdoor temperature zone * prohibition zone Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
9. Group connection NOTE: Group control cannot be used together with Wireless LAN adapter. Installation procedure for group control system: A number of indoor units can be operated at the same time using a single remote controller. NOTE: When different type of indoor units (such as wall mounted type and cassette type, cassette type and duct type, or other combinations) are connected using group control system, some functions may no longer be available.
11. Function settings To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 11-1. Function settings by using remote controller Some function settings can be changed on the remote controller. After confirming the setting proce- dure and the content of each function setting, select appropriate functions for your installation envi- ronment.
Page 38
NOTES: • The air conditioner custom code is set to prior to shipment. • If you do not know the air conditioner custom code setting, try each of the custom codes ( → → → ) until you find the code that operates the air conditioner. - 34 - 11-1.
Page 39
¢ Contents of function setting Each function setting listed in this section is adjustable in accordance with the installation environ- ment. NOTE: Setting will not be changed if invalid numbers or setting values are selected. Function setting list Function no. Functions Remote controller address setting Filter sign...
Page 40
2) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03). Function number Setting value Setting description Factory setting...
Page 41
4) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to Both “01”. Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
Page 42
7) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 8) External input control "Operation/Stop" mode or "Forced stop" mode can be selected. Function number Setting value Setting description...
Page 43
11) Control switching of external heaters Sets the control method for external heater to be used. For details, refer to Chapter 8-4. "Details of function" on page 18 Function Factory Setting value Setting description number setting Auxiliary heater control 1 ♦...
Page 44
14) Outdoor temperature zone boundary temperature B Setting required if changing of the outdoor temperature setting for heat pump only zone is required when auxiliary heater control by outdoor temperature 1 is performed on the indoor unit. For details, refer to Chapter 8-4. "Details of function"...
11-2. Custom code setting for wireless remote controller To interconnect the air conditioner and the wireless remote controller, assignment of the custom code for the wireless remote controller is required. NOTE: Air conditioner cannot receive a signal if the air conditioner has not been set for the custom code.
13. Optional parts 13-1. Controllers Exterior Part name Model name Summary Easy finger touch operation with LCD panel. Backlit LCD enables easy operation in a dark room. Wired remote UTY-RNRYZ* Wire type: Non-polar 2-wire controller Optional communication kit is necessary for installation. High visibility and easy operation.
13-2. Others Exterior Part name Model name Summary Required when external device is connected. External UTY-XWZXZ5 Optional communication kit is connect kit necessary for installation. External input Use to connect with external devices UTY-XCSXZ2 and output PCB and air conditioner PCB. Communication Use to connect Non-polar 2-core wired UTY-TWRXZ2...
1. Specifications Type Inverter heat pump Model name AOTG09KMTC AOTG12KMTC Power supply 240 V ~ 50 Hz Power supply intake Outdoor unit Available voltage range 198—264 V Starting current Cooling 1,530 1,770 Airflow rate Heating 1,315 1,315 Type × Q'ty Propeller fan ×...
2. Dimensions 2-1. Models: AOTG09KMTC and AOTG12KMTC Unit: mm 4-M10 hole Pitch of bolts for installation Top view Side view Front view Side view Airflow Drain port Ø42 Bottom view Side view (Valve part) - 47 - 2-1. Models: AOTG09KMTC and AOTG12KMTC 2.
3. Installation space 3-1. Models: AOTG09KMTC and AOTG12KMTC ¢ Space requirement Provide sufficient installation space for product safety. CAUTION Keep the space shown in the installation examples. If the installation is not performed accordingly, it could cause a short circuit and result in a lack of operating performance.
Page 53
Multiple outdoor unit installation • Provide at least 250 mm of space between the outdoor units if multiple units are installed. • When routing the piping from the side of an outdoor unit, provide space for piping. • No more than 3 units must be installed side by side. When 3 units or more are arranged in a line, provide the space as shown in the following ex- ample “When an obstruction in the upper space:”.
Page 54
Outdoor units installation in multi-row Unit: mm Single parallel unit arrangement Multiple parallel unit arrangement 100 or more 200 or more 1,000 or more 2,000 or more 200 or more 400 or more 500 or more 1,000 or more 200 or more 250 or more 1,000 or more...
6. Capacity compensation rate for pipe length and height difference Height difference H Indoor unit is higher than outdoor unit Indoor unit is lower than outdoor unit Outdoor unit Indoor unit Outdoor unit Indoor unit Connection pipe Connection pipe 6-1. Models: AOTG09KMTC and AOTG12KMTC NOTE: Values mentioned in the table are calculated based on the maximum capacity.
9-2. Sound level check point Rear Microphone Microphone Airflow Side view Rear view NOTE: Detailed shape of the actual outdoor unit might be slightly different from the one illustrated above. - 57 - 9-2. Sound level check point 9. Operation noise (sound pressure)
10. Electrical characteristics Model name AOTG09KMTC AOTG12KMTC Voltage 240 ~ Power supply Frequency Max operating current* Starting current Circuit breaker current Power cable Cross- Wiring spec. * Connection sectional area cable* Limited wiring length *1: Maximum operating current is the total current of the indoor unit and the outdoor unit. *2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
11. Safety devices Model Type of Protection form protection AOTG09KMTC AOTG12KMTC 250 V, 20 A Circuit Current fuse (Main PCB) 250 V, 5 A protection 250 V, 3.15 A 100±15°C Activate Fan motor stop Fan motor Terminal protection program protection 95±10°C Reset Fan motor restart...