Information - Strain Relief Detail For Output Wiring; Figure 7 Chamber Wiring; Figure 8 Strain Releif For Output Wiring - ABB RP450 Quick Start Manual

Integrated pole mount
Table of Contents
QUICK START GUIDE
3. After the dead front cover is removed, open the necessary insulators. Wiring
chamber will look like as shown in figure 7. The AC wiring comes in at the bottom
and is routed through the channel on the right up to the AC wiring compartment.
The DC wiring is connected in the DC wiring compartment and is routed out the
bottom through the strain reliefs

Information - Strain relief detail for output wiring

There are 9 strain relief attached to unit
6 Strain Relief for DC Output wire breakers
1 Strain Relief for Signal wires
1 Strain Relief for DC Ground
One unused should be populated with the plug which is part of ship loose kit
Strain Relief rated for 0.220-0.290" (5.6-7.4mm) cable diameter range and the following UL cable types:
S, SE, SEO, SEOOW, SEOW, SJ, SJEOOW, SJEOW, SJO, SJOO, SJOOW, SJOW, SJTEOOW, SJTEOW, SJTO, SJTOO,
SJTOOW, SJTOW, SJTW, SO, SOO, SOOW, SOW, SV, SVE, SVEO, SVO, SVOO.
Page 13
© 2021 ABB. All rights reserved.
Figure 8 Strain relief for output wiring

Figure 7 Chamber wiring

Strain relief