ABB J2012001 Quick Start Manual
ABB J2012001 Quick Start Manual

ABB J2012001 Quick Start Manual

3u din distribution shelf - 19 in rack mount

Quick Links

QUICK START GUIDE
3U DIN Distribution Shelf - 19 in Rack Mount
J2012001 - multiple models - See SPS, NE, or CP Brochure for details of
models
The distribution shelf may be installed as a component of a power systems or as a stand-alone remote distribution
(cabled input power). Some models include battery connections. Some models include battery connections and
battery contactors.
Controller: All power systems have a controller. It may be located in the primary rectifier shelf or in the distribution
shelf. If the power system has a primary rectifier shelf (with controller), install the distribution shelf immediately
above it.
Refer to SPS, Infinity S (NE S), or CPL Brochure for details, circuit breakers, and accessories.
Torque wrench (0-40Nm)
Screw Drivers - Phillips and flat
Sockets - metric and inch
Page 1
© 2021 ABB. All rights reserved.
17" deep Shelf (NE & CP compatible)
11" deep Shelf (SPS compatible)
Wire cutters and strippers
Cable crimpers
loading

Summary of Contents for ABB J2012001

  • Page 1 QUICK START GUIDE 3U DIN Distribution Shelf - 19 in Rack Mount J2012001 - multiple models - See SPS, NE, or CP Brochure for details of models 17” deep Shelf (NE & CP compatible) 11” deep Shelf (SPS compatible) The distribution shelf may be installed as a component of a power systems or as a stand-alone remote distribution (cabled input power).
  • Page 2 Lug Landings - 2 x 1/4” on 5/8” center, 0.7” (18mm) max. tongue width. Connect cables with suitable lugs to -48V & RETURN. Torque to 4Nm (35in-lb) - 8mm (8mm)socket. -48V bus Connections Inter-shelf bus covers removed Page 2 © 2021 ABB. All rights reserved.
  • Page 3 A. Install Battery Breaker Kits - skip if battery breakers are installed or batteries are not present 1. Connect alarm wire to battery breaker (wires provided) Connect Fastons to breaker terminals. Terminal 11 - Red Terminal 12 - Black Page 3 © 2021 ABB. All rights reserved.
  • Page 4: Connect Batteries

    Break off Cable Entry Tabs as necessary. Lug Adapter Battery Connection Alarm Card HDR3 Battery Return Bus Release Levers Push to release DIN Rail Engagement Breaker Bottom Connections Bus Tabs Alarm Wires Page 4 © 2021 ABB. All rights reserved.
  • Page 5 6. Repeat for additional loads. Step 8 - Label Connections ID label is in front of the breakers or on the door. Mark each connected circuit identification on the ID label. ID Label Example Page 5 © 2021 ABB. All rights reserved.
  • Page 6: Step 10 - Install Controller

    2. Controller Backplane connections. a. J1-2 Alarms - detachable block - Wire to office alarms and signals. See Information: Alarm Connections for alarm connection details b. J5 LAN - Connect to Ethernet network. Page 6 © 2021 ABB. All rights reserved.
  • Page 7 ABB Device Comm Cable Controller Cable Bushing Bottom View Rectifier Shelf without controller typical ABB Device Comm Cable - a shipped ABB Device Comm Cable - to Rectifier Shelf Controller in Distribution Shelf Page 7 © 2021 ABB. All rights reserved.
  • Page 8 Change alarm descriptions via LAN port (Web pages) or Craft port (EasyView2) when required. Pin/ Connector Alarm Outputs Alarm Inputs Input: SPD Fail 1 Only with 6 relay controllers (...6R…). 2 Returns for R1 and R4 are bridged. Other returns are isolated. Page 8 © 2021 ABB. All rights reserved.
  • Page 9 These documents are available at abbpowerconversion.com Document Title CC848815341 Pulsar Edge Controller Family Product Manual Galaxy Pulsar Edge Quick Start Guide SPS Brochure 850035894 Infinity S (NE S) Brochure Compact Power Line (CPL) Brochure Page 9 © 2021 ABB. All rights reserved.
  • Page 10: Safety Statements

    Grounding - Connect the equipment chassis directly to ground. In enclosed equipment cabinets connect to the cabinet AC service ground bus. In huts, vaults, and central offices connect to the system bonding network. Page 10 © 2021 ABB. All rights reserved.
  • Page 11 Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems, including batteries and cables, typically found in telecommunications utility rooms, can affect medical electronic devices, such as pacemakers. Effects decrease with distance. Page 11 © 2021 ABB. All rights reserved.