ABB RP450 Quick Start Manual
ABB RP450 Quick Start Manual

ABB RP450 Quick Start Manual

Integrated pole mount
Table of Contents

Quick Links

QUICK START GUIDE
RP450 Integrated Pole Mount
Quick Start Guide
Important safety instructions
Save these instructions
This equipment is not suitable for use in locations where
children are likely to be present
Read and follow all safety statements, warnings, and
precautions in this manual before installing, maintaining or
repairing this equipment.
Document - 8600452418P
Page 1
© 2021 ABB. All rights reserved.
consignes de sécurité importantes
Conservez ces instructions
Cet équipement n'est pas adapté à une utilisation dans des
endroits où des enfants sont susceptibles d'être presents
Lisez et suivez toutes les consignes de sécurité, les
avertissements et les précautions de ce manuel avant
d'installer, d'entretenir ou de réparer cet équipement.
Table of Contents
loading

Summary of Contents for ABB RP450

  • Page 1 Read and follow all safety statements, warnings, and precautions in this manual before installing, maintaining or avertissements et les précautions de ce manuel avant repairing this equipment. d'installer, d'entretenir ou de réparer cet équipement. Document - 8600452418P Page 1 © 2021 ABB. All rights reserved.
  • Page 2: Table Of Contents

    Information - for Replacement Applications ..................20 Information - Touch Up Paint ........................ 20 Parts List ..............................21 Specifications and Application ......................21 Ordering Information ..........................21 Change History ............................22 Disclaimer ............................... 23 Page 2 © 2021 ABB. All rights reserved.
  • Page 3 Figure 12 AC Input Wiring ........................16 Figure 13 Final Wire Dressing ........................ 17 Figure 14 Aalrm Connections ......................... 18 Figure 15 DC output connections ......................18 Figure 16 AC Input connections ......................19 Page 3 © 2021 ABB. All rights reserved.
  • Page 4: Important Safety Instructions

    11. This equipment is to be mounted directly and permanently above non-combustible surface, such as concrete or metal. 12. WARNING: Equipment is not designed to charge an external battery source. This equipment is not suitable for use in locations where children are likely to be present Page 4 © 2021 ABB. All rights reserved.
  • Page 5: Consignes De Sécurité Importantes

    12. AVERTISSEMENT : L'équipement n'est pas conçu pour charger une source de batterie externe. 13. Cet équipement ne convient pas à une utilisation dans des endroits où des enfants sont susceptibles d'être présents Page 5 © 2021 ABB. All rights reserved.
  • Page 6: Precautions

    Personnel with electronic medical devices need to be aware that proximity to DC power and distribution systems can affect medical electronic devices, such as pacemakers. Effects decrease with distance. • If equipment is mounted 10 ft high or above, use an elevated platform to access equipment. Page 6 © 2021 ABB. All rights reserved.
  • Page 7: Précautions

    CC peut affecter les appareils électroniques médicaux, tels que les stimulateurs cardiaques. Les effets diminuent avec la distance. • Si l’équipement est monté à 10 pieds de haut ou plus, utilisez une plate-forme surélevée pour accéder à l’équipement. Page 7 © 2021 ABB. All rights reserved.
  • Page 8: Safety

    It includes the product serial number and input - output specifications of the cabinet. 1600361512A, RP450-48-PS1-DC6B-SRG 1600408704A, RP450-48-PS1-DC6F-SRG Figure 2 Product ID Label Information Customer Care +1 877 546-3243 Reference Documents RPxxx-48-PSx-DC6xx-SRG-AD Page 8 © 2021 ABB. All rights reserved.
  • Page 9: Introduction

    Isolated alarm contacts are available for DC Fault and AC Fault. • AC FIELD WIRING AC BREAKER SECTION AC SPD DC BREAKERS (OR FUSES) DC SPD DC FIELD WIRING SECTION AC CONDUIT FOR INPUT Page 9 © 2021 ABB. All rights reserved.
  • Page 10: Information - Tools Required

    • • 3 x TERMINAL BLOCK, 3 POS 10-32 FLANGE NUT • • LUG, 6AWG, 2 HOLE, #10 7 x HOLE PLUG • • TERMINAL BLOCK, 2 POS 9 x STRAIN RELIEF Page 10 © 2021 ABB. All rights reserved.
  • Page 11: Step 1 - Mount Unit To Pole

    3. Use ¾” inch wide straps to mount the unit to the pole approximately as show in view to the right. Lift Hook Lifting 2.5mm diameter Harness Samson Amsteel Blue Dyneema 25” 635mm Straps Attach lower Strap before removing Lifting harness Knot Figure 3 Mounting unit to pole Page 11 © 2021 ABB. All rights reserved.
  • Page 12: Step 2 - Ground The Unit

    2. Use a slotted screwdriver to loosen the 4 captive screws of the upper dead-front cover, then remove the upper dead- front cover. UPPER DEAD-FRONT SCREWS Page 12 Figure 6 Upper dead front screws © 2021 ABB. All rights reserved.
  • Page 13: Information - Strain Relief Detail For Output Wiring

    S, SE, SEO, SEOOW, SEOW, SJ, SJEOOW, SJEOW, SJO, SJOO, SJOOW, SJOW, SJTEOOW, SJTEOW, SJTO, SJTOO, SJTOOW, SJTOW, SJTW, SO, SOO, SOOW, SOW, SV, SVE, SVEO, SVO, SVOO. Strain relief Figure 8 Strain relief for output wiring Page 13 © 2021 ABB. All rights reserved.
  • Page 14: Step 4 - Wire The Dc Output

    One wire carries +. The other carries the terminal block. One wire carries +. The other – 48V. carries –48V. GMT fuse 0.6”(16mm)Return 0.6”(16mm)Return 0.35”(9mm)CB 0.5”(13mm)CB Figure 9 DC Output wiring Page 14 © 2021 ABB. All rights reserved.
  • Page 15: Step 5 - Wire The Alarms

    When connecting to AC mains, follow all local and national wiring rules. Caution: Ensure that wires do not come in contact with sharp or rough surfaces that may damage insulation and cause a short circuit. Figure 11 AC Feed Page 15 © 2021 ABB. All rights reserved.
  • Page 16: Configured As Service Entrance

    10 AWG or smaller, 40 in-lb for 8 AWG using a flat bladed screw driver. flat bladed screw driver. 12. Pull wire to verify. 12. Pull wire to verify. Bond Jumper Bond Main Ground Washer Figure 12 AC Input Wiring Page 16 Neutral © 2021 ABB. All rights reserved.
  • Page 17: Step 7 - Final Wire Dressing And Close The Door

    5. Confirm that DC is present on the outputs by observing a signal from the repeater(s) or radio(s). 6. Test the alarm contacts by cycling the AC to off. Observe that AC and DC alarms are active when no AC is present. Page 17 © 2021 ABB. All rights reserved.
  • Page 18: Information - Electrical Connections

    When the output is short circuited, the unit will cycle on and off with a interval of about 14 seconds. Short circuit hiccup is disabled for the first 20 seconds after start up to support the inrush requirements of the load. - 48V Figure 15 DC output connections Page 18 © 2021 ABB. All rights reserved.
  • Page 19: Ac Input Connections

    AC SPD, DC SPD, or both SPDs have failed. AC is present and breaker is Closed/On, and both the DC and DC Fail And SPD Fail SPD Fail are present. Normal Green No Alarms and everything Normal. Page 19 © 2021 ABB. All rights reserved.
  • Page 20: Information - External Electrical Equipment

    Information - Touch up paint Should any part of the unit coating be damaged, repaint using: LVP Powder and Paints RAL7035 Touch Up Paint - Light Grey - 12 oz Spray Can. Page 20 © 2021 ABB. All rights reserved.
  • Page 21: Parts List

    Enclosure is rainproof. • Internal rectifier is in an IP 6x enclosure. Ordering Information Ordering Code Model Power (W) Redundancy Backup Load Breakers Load Fuses Surge 1600361512A RP450-48-PS1-DC6B-SRG NONE 1600408704A RP450-48-PS1-DC6F-SRG NONE Page 21 © 2021 ABB. All rights reserved.
  • Page 22: Change History

    DC breaker is removed and 2A, 3A Variants of DC breaker are added in part list, Warning label added in safety section, Updated Product id label 09/02/2022 Updated figure 16 AC input connections Page 22 © 2021 ABB. All rights reserved.
  • Page 23: Disclaimer

    With regard parties or utilization of its contents – in whole or in parts – is to purchase orders, the agreed particulars shall prevail. ABB forbidden without prior written consent of ABB. does not accept any responsibility whatsoever for potential errors or possible lack of information in this Copyright©...