Mitsubishi Electric Melsec-F FX3GC Series User Manual page 57

Hide thumbs Also See for Melsec-F FX3GC Series:
Table of Contents
FX
/FX
/FX
/FX
/FX
3S
3G
3GC
3U
3UC
Built-in Positioning Functions
2. High-speed output special adapter
Application
Pulse train sig-
nal/forward
rotation pulse
train
(pulse output
destination)
Direction sig-
nal/reverse
rotation pulse
train
(rotation
direction
signal)
CLEAR signal
*1.
Specify an output number for transistor output.
PLC User's Manual - Positioning Control Edition
Output number
Terminal
1st
2nd
Y0/2+
Y000
Y002
Y0/2-
Y1/3+
Y001
Y003
Y1/3-
Y4/6+
Y004
Y006
Y4/6-
Y5/7+
Y005
Y007
Y5/7-
*1
All output points
1.5 Assignment of Input/Output Numbers
Remarks
Connect a line to determine the pulse train signal or the forward
rotation pulse train for the 1st axis of each high-speed output
special adapter.
For the 1st adapter, specify Y000 as the pulse output destination
of the positioning instruction. For the 2nd adapter, specify Y002
as the pulse output destination of the positioning instruction.
Connect a line to determine the pulse train signal or the forward
rotation pulse train for the 2nd axis of each high-speed output
special adapter.
For the 1st adapter, specify Y001 as the pulse output destination
of the positioning instruction. For the 2nd adapter, specify Y003
as the pulse output destination of the positioning instruction.
Connect a line to determine the direction signal or the reverse
rotation pulse train for the 1st axis of each high-speed output
special adapter.
For the 1st adapter, specify Y004 as the rotation direction signal
of the positioning instruction. For the 2nd adapter, specify Y006
as the rotation direction signal output of the positioning
instruction.
Connect a line to determine the direction signal or the reverse
rotation pulse train for the 2nd axis of each high-speed output
special adapter.
For the 1st adapter, specify Y005 as the rotation direction signal
output of the positioning instruction. For the 2nd adapter, specify
Y007 as the rotation direction signal output of the positioning
instruction.
Connect a line if it is necessary to use the DSZR/ZRN instruction
to output the CLEAR signal.
Using the CLEAR signal device specification function, specify the
output number for the transistor output. In this case, do not
specify an output device if the device is already specified for
outputting the rotational direction signal.
 For details on the CLEAR signal
method, refer to Subsection 4.3.4.
The CLEAR signal device specification register depends on the
pulse output destination as shown in the following table:
Pulse output destination
Y000
Y001
Y002
Y003
Point:
The CLEAR signal output that is initially set for the DSZR/ZRN
instruction is the same output as the direction signal (rotation
direction signal, reverse pulse train). Be sure to specify an output
number of another transistor output using the CLEAR signal
device specification function.
1 Outline
device specification
CLEAR signal device
specification register
D8464
D8465
D8466
D8467
B - 13