Honeywell GENT S4 Data And Installation

Honeywell GENT S4 Data And Installation

Mains powered interface
Hide thumbs Also See for GENT S4:

Quick Links

Data and Installation
S4 Mains Powered Interface
(S4-34440-02 & S4-34440-12)
The S4 Mains powered interface units (Part No's:
S4-34440-02 and S4-34440-12) are EN54-4
compliant battery backed power supplies that can
be directly connected to the Vigilon and Nano loop
and also have highly flexible interfacing capability.
The 4 channels can be individually configured to
provide Output and Input interface in various
configuration modes, to control external equipment
and receive input to allow the fire system to make
decisions and take actions. It is now possible to
have combined inputs and outputs giving a total of
8 external circuits connected (e.g. 4 sector outputs
and 4 confirmation inputs). The units have room to
accommodate optional modules on to DIN rails. It
has a configurable auxiliary power output that is
derived from its self contained mains power supply
unit, which is battery backed to continue to deliver
power in the event of mains supply failure.
Note a Nano system loop can only accept S4-34440-02.
Technical Data
Standards -
EN54:part 4:1998
designed to meet
EN54:part 17:2005
EN54:part 18:2005
Overall
478mm x 322mm x 128mm
dimensions
Assembled weight
7Kg (excluding batteries and
(approximate)
optional components fitted)
Enclosure
Steel
Colour
RAL7024 Graphite Grey
(fine textured)
Storage
-20 to 70ºC
temperature
Ambient operating
-10 to 45°C
temperature
4188-968 issue 2_Part 1_09-10_S4 mains interface
www.acornfiresecurity.com
www.acornfiresecurity.com
Relative Humidity
up to 95%
(Non condensing)
Temperature 5 - 45°C
Ingress Protection IP31(estimated)
Operating voltage
230V 50Hz +10% -6%
Rated current
0.7A
Input modes
Input can be fault monitored,
voltage free, contacts OR
conventional detection zone
circuit. Refer to the
commissioning information for
more details.
Zone
Nominal voltage
16V or 22.5V (default) ±15%
20mA per zone (default)
Quiescent current
Zone short circuit current
limited to < 30mA
EN54 compliance limitation:
32 devices OR Maximum of
20 diode bases per zone
Output modes
Outputs are monitored 24V
(nominal) 0.5A OR LED drive.
Refer to the commissioning
information for more details
Confirmation
It is possible to configure all
modes
Inputs and Outputs as
confirmation channels
Sector and
Sector and Auxiliary Outputs
Auxiliary Outputs
0.5A max each @ 24V +/-3V,
electronically current limited to
approximately 1A at 25
Maximum total output current:
S4-34440-02 = 1.5A
S4-34440-12 = 2.5A
Auxiliary power output:
12V / 24V ±0.5V (S4-34440-12)
or
24V
±3V (S4-34440-02)
Batteries
Two types:
2 x 12V 2.1Ahr (1Kg each)
for S4-34440-02
2 x 12V 12Ahr (4.31Kg each)
for S4-34440-12
Compatible
Vigilon
# Backward compatibility
is possible, refer to your
Commissioning tool ³ V1.27
supplier
Nano
Commissioning tool ³ 2.x
by Honeywell
o
C
:MCC ³ V4.43 / V3.97
#
:LPC ³ V4.41 / V3.97
:MC ³ V2.50
1
loading

Summary of Contents for Honeywell GENT S4

  • Page 1 Data and Installation S4 Mains Powered Interface by Honeywell (S4-34440-02 & S4-34440-12) Relative Humidity up to 95% (Non condensing) Temperature 5 - 45°C Ingress Protection IP31(estimated) Operating voltage 230V 50Hz +10% -6% Rated current 0.7A Input modes Input can be fault monitored,...
  • Page 2 www.acornfiresecurity.com Data and Installation S4 Mains powered interface unit EN54-17 : 2005 0.4A C max Features (section 4.8) S max ¨ data: Fail-safe operation 20mA L max A fail-safe operation is available on all sectored 0.1W SO max C max outputs, if loop communications are lost for a defined SO min duration then the sector outputs will be turned ON.
  • Page 3: Installation

    www.acornfiresecurity.com S4 Mains powered interface unit Data and Installation Mains supply Installation The mains supply cable must be a standard fire resisting type and should meet PH30 classification, such as any The batteries are supplied in a separate pack. of the standard and enhanced loop cable. Requires a Spare Parts packages minimum conductor cross sectional area of 0.75mm Fuse 3.15A AS Ceramic...
  • Page 4 Do not burn. Gent by Honeywell reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions of changes.
  • Page 5: Commissioning Information

    Commissioning information S4 Mains powered interface by Honeywell (S4-34440-02 & S4-34440-12) Factory settings ¨ The S4 Mains powered interface channels 1 - 4 are all set to UNUSED. ¨ The Auxiliary output is off and is unaffected by mains failure or fire reset.
  • Page 6 www.acornfiresecurity.com Commissioning information S4 Mains powered interface unit How to install batteries and Power up The following illustration shows how to connect a pair of 12V 12Ah batteries for S4-34440-12 or 12V 2.1Ah batteries for S4-34440-02 into a S4 Mains powered interface unit. The numbers j, k, l.. shows the order in which to carry out the installation.
  • Page 7 www.acornfiresecurity.com S4 Mains powered interface unit Commissioning information S4 Mains Powered Interface - Config. menu Menu option you can use this option to.. notes S4 Mains Powered ...to configuring the S4-34440-02 Interface... and S4-34440-12 Mains powered interface units. ‚ƒ„ ... Operation (The numbers shows the order in which to the make selections and enter appropriate data).
  • Page 8: Output Mode

    www.acornfiresecurity.com Commissioning information S4 Mains powered interface unit Output mode This is when a channel is configured as an output and the channels input terminals are not used. Mode settings notes Output Output type The Sectored output is used to power a wide range of alarm products such as sounders, bells door holders and relay.
  • Page 9 www.acornfiresecurity.com S4 Mains powered interface unit Commissioning information Zone Input mode This example shows how to set a channel as a Zone input. Mode settings notes Zone Input Zone Input Type The Zone Input Type monitors 'conventional' detectors and call points, with manual call points having 470 ohms resistor in series with Normally Open contacts.
  • Page 10 www.acornfiresecurity.com Commissioning information S4 Mains powered interface unit Supervisory Input mode This example sets the respective channel as a Supervisory input. Mode settings notes Supervisory input Input delay The Input Delay is the time before the input is accepted by the interface, this will filter any noise or spurious signals, commonly know as "bounce".
  • Page 11 www.acornfiresecurity.com S4 Mains powered interface unit Commissioning information Confirmation Input mode The purpose of a Confirmation Input is to allow the system to monitor the correct operation of an output, which relies on external equipment sending back the correct signal. In this mode use a 470ohms end-of-line resistor with another 470ohms resistor being switched in parallel across the Z+ and Z- terminals to provide the feedback signal.
  • Page 12 www.acornfiresecurity.com Commissioning information S4 Mains powered interface unit Confirmation Output mode A channel is configured as a confirmation output and is associated with an input at another channel, but not its own channel. Mode settings notes Confirmation Output Output type: See page 4.
  • Page 13 www.acornfiresecurity.com S4 Mains powered interface unit Commissioning information Output with Supervisory Input mode This is when a channel is configured as an output and the channels input terminals are Supervisory Input. Mode settings notes Output / Supervisory Output Type See page 4. input Sync.
  • Page 14 www.acornfiresecurity.com Commissioning information S4 Mains powered interface unit Output with Fire input mode This is when a channel is configured as an output and the channels input terminals are Fire Input. Mode settings notes Output / Fire input Output Type See page 4.
  • Page 15 www.acornfiresecurity.com S4 Mains powered interface unit Commissioning information Confirmation Output with Zone Input mode This example shows how to set a confirmation output when there is a state change on the associated Zone input. Mode settings notes Confirmation Zone Input Type See page 5.
  • Page 16 www.acornfiresecurity.com Commissioning information S4 Mains powered interface unit Confirmation Output with Supervisory Input mode This example shows how to set a confirmation output when there is a state change on the associated Supervisory input. Mode settings notes Confirmation Output type: See page 4 Output/Supervisory Input...
  • Page 17 www.acornfiresecurity.com S4 Mains powered interface unit Commissioning information Confirmation Output with Fault Input mode This example shows how to set a confirmation output when there is a state change on the associated fault input. Mode settings notes Confirmation Output Type: See page 4.
  • Page 18 www.acornfiresecurity.com Commissioning information S4 Mains powered interface unit Auxiliary output The interface has an auxiliary output rated at 1A max. The output voltage can be programmed as unregulated 24V (+/-3V) on the S4-34440-02 or regulated 12V/24V (+/-0.5V) on the S4-34440-12. Mode settings notes...
  • Page 19 www.acornfiresecurity.com S4 Mains powered interface unit Commissioning information This page has been intentionallly left blank. 4188-968 issue 2_Part 2_09-10_S4 mains interface www.acornfiresecurity.com...
  • Page 20 www.acornfiresecurity.com Commissioning information S4 Mains powered interface unit www.acornfiresecurity.com...

This manual is also suitable for:

S4-34440-02S4-34440-12