    TABLE OF CONTENTS PRODUCT DISPOSAL (WEEE) ....................5 THE RECIPIENTS OF THIS MANUAL ..................5 PACKAGE ..........................6 TECHNICAL DATA ......................... 7 INSTALLATION ........................8 XWEB ..........................8 CONTROLLERS ......................10 5.2.1 CONFIGURATION FOR XC400/600/800/900 and XH200/300/400 SERIES ......12 5.2.2 CONFIGURATION FOR XJA/XJP/XJM MODELS ............
  • Page 4 CAUTION: TO PREVENT FLAMES FROM DEVELOPING OR ELECTRIC SHOCK, AVOID ANY CONTACT BETWEEN THIS DEVICE AND RAIN OR WATER CAUTION: TO REDUCE THE RISK OF ELECTRIC SHOCK, DO NOT REMOVE THE COVER IT DOES NOT CONTAIN ANY PARTS THAT REQUIRE SERVICING BY THE USER ALWAYS HAVE QUALIFIED STAFF PERFORM THE PROCEDURES.
  • Page 5: Product Disposal (Weee)

    CAUTION The customer shall bear full responsibility and risk for product configuration in order to achieve the results pertaining to installation and/or final equipment/system. Upon the customer's request and following a specific agreement, Dixell s.r.l. may be present during the start-up of the final machine/application, as a consultant, however, under no circumstances can the company be held responsible for the correct operation of the final equipment/system.
  • Page 6: Package

    PACKAGE Bef ore opening the package make sure that the packaging is intact and that there is no s ign of impact or tampering. Before starting any operation, it is necessary to check that the XWEB box contains: • 1 XWEB 5000 PRO unit •...
  • Page 7: Technical Data

    TECHNICAL DATA Power supply 100-230 V Power 60 W Voltages and maximum current applicable to the AUX1-2-3 AUX terminals 1-2-3 AUX1 AUX2-3 Operating conditions (temperature, humidity, 0/45°C R.H.5÷95% (non-condensing) special conditions) Electrical safety LVD - COUNCIL DIRECTIVE 2014/35/EU Electromagnetic compatibility EMC - COUNCIL DIRECTIVE 2014/30/EU Rechargeable and non-removable lithium battery.
  • Page 8: Installation

    INSTALLATION XWEB For installation, the XWEB-EVO system must not be opened in any way. If the box is opened, the warrant y will lapse. XWEB-EVO can be installed in various ways based on the type of user interface acc es s t hat y ou wish t o provide for the final user.
  • Page 9 Colour Description Green On when the system is powered Blue On when the disc executes physical writing operations Blue On when the system is recording data Ser1/Ser2 Blue On when the system is reading and/or writing on serial port 485 Blue On when the system runs operations with the analogue modem DI1/DI2...
  • Page 10: Controllers

    CONTROLLERS XWEB has at least one RS485 serial port, on which the line of the controller devices can be c onnected. If there are more serials, more device lines can be served. Most Dixell controller devices are equipped with an RS485 serial output and can be connected wit hout t he need f or any additional module or connection cable.
  • Page 11 • Do not branch into the line: Correct Mistaken • Keep the serial cable away f rom power cables and any possible source of electromagnetic disturbance. Mount the supplied ferrites on the serial ports as shown in the figure • Do not connect the shield of the serial cable to the earth of the electrical system •...
  • Page 12: Configuration For Xc400/600/800/900 And Xh200/300/400 Series

    XWEB. To activate the EOL resistor, insert the jumper in position 2 (word TERM). DO NOT insert the jumper if the XWEB is in the middle of the RS485 line. Notes on the use of polarization resistors (POL-, POL +) In order to avoid false signals on the bus, polarization resistors must be inserted.
  • Page 13: Local Connectivity

    LOCAL CONNECTIVITY Local access with a screen, mouse and keyboard directly connected to the XWEB is the most common and most f requently used type of access f or the user int erf ace. The system can work even without these peripherals connected and it is possible, for example, to use this mode only for the initial configuration of the system;...
  • Page 14: Desktop Software Requirements (Pc)

    The terminal used must comply with and support the minimum characteristics for the installation and use of the f ollowing software. DESKTOP SOFTWARE REQUIREMENTS (PC) Browser Support Minimum Version Microsoft Edge SUPPORTED Mozilla Firefox SUPPORTED Google Chrome SUPPORTED Apple Safari SUPPORTED 10.1+ Opera...
  • Page 15: Connectivity With Cross Cable

    CONNECTIVITY WITH CROSS CABLE Local access from the PC is the fastest way to manage setup. It is possible to connect a PC to X WEB -EV O through the network interface supplied with an ‘RJ45 Ethernet connector’. The connection between t he t wo must be set up using a cross network cable (aka 'cross cable').
  • Page 16: Intranet Connectivity ("Or Lan Connection") And Vpn

    INTRANET CONNECTIVITY (“OR LAN CONNECTION”) AND VPN This type of connection will allow you to access XWEB from any PC connected to the local network. This type of connection must also be used to configure the XWEB for connection from the internet via VPN (Virtual Private Network).
  • Page 17: Internet Connectivity On Public Ip

    INTERNET CONNECTIVITY ON PUBLIC IP This type of connection will allow you to directly access XWEB from any PC connected to the internet without having to install - on your PC - any additional software. Attention: the connection to the Internet presumes to be managed by qualified personnel and / or by the network administrator.
  • Page 18: Wifi Connectivity

    WIFI CONNECTIVITY This type of connection will allow you to directly access XWEB f rom a device equipped with a Wi-Fi connection, or to allow XWEB to access an already configured Wi-Fi network. A prerequisite for these t ypes of connectivity is the installation of the WIFI dongle in the XWEB USB port. ATTENTION: Only use dongles officially supported by this monitoring unit.
  • Page 19: Operative Procedures

    ___________________________ 10. TRADEMARKS Consider It Solved and Intelligent Store are trademarks and Emerson Climate Technologies and the Emerson Climate Technologies logo are service marks and trademarks of Emerson Electric Co. Windows and Internet Explorer are registered trademarks of Microsoft Corporation in the United Stat es and other countries.
  • Page 20: Notes

    11. NOTES ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ ______________________________________________________________________________________ 1592010820 XWE B5000 PRO STP GB r1.0 25.11.2020.docx XWEB5000 P RO 20/20...